Lightolier C7E17VW Folheto

Página de 2
Calculite
®
HID Downlight
C7E17VW
Page 1 of 2
7" Aperture, ED17 (Enclosed), Ceramic Metal Halide, Wide Beam
Job Information
Type:
Job Name:
Cat. No.:
Lamp(s):
Notes:
Lightolier 
a Genlyte Thomas Company
www.lightolier.com
631 Airport Road, Fall River, MA 02720 • (508) 679-8131 • Fax (508) 674-4710
We reserve the right to change details of design, materials and finish.
© 2004 Genlyte Thomas Group LLC (Lightolier Division) • AO5O4
Ceiling Cutout: 8" (203 mm) Dia.
Reflector Trim
Frame-In Kit
Lamp (Coated, Ceramic MH)
C7E17VW CLW
Specular Clear, White Painted Flange.
CLP
Specular Clear, Matching Flange.
CCDW
Comfort Clear Diffuse, White Painted Flange.
CCDP
Comfort Clear Diffuse, Matching Flange.
CCZW
Champagne Bronze, White Painted Flange.
CCZP
Champagne Bronze, Matching Flange.
C770MHE1
Electronic 120V
70W ED17, BD17 (Enclosed)
C770MHE2
Electronic 277V
70W ED17, BD17 (Enclosed)
C710MHE1
Electronic 120V
100W ED17, BD17 (Enclosed)
C710MHE2
Electronic 277V
100W ED17, BD17 (Enclosed)
C770MHU
Magnetic 120V/277V
70W  ED17, BD17 (Enclosed)
C710MHU
Magnetic 120V/277V
100W ED17, BD17 (Enclosed)
Features
1. Upper Reflector: Clear anodized aluminum, 0.040” (16-ga.). Provides wide
beam distribution.
2. Aperture Cone: Provides 50° visual cut-off to lamp and lamp image; 
self-flange in painted white or aperture-matching polished flange. Consult
factory for other finishes.
3. Lamp Guard: High heat resistant glass as required by code.
4. Socket Housing: Galvanized steel, snaps onto upper reflector for secure
attachment without tools; assures proper lamp alignment to optics for 
consistent performance.
5. Mounting Frame: 0.048" (18-ga.) galvanized steel includes pre-installed
mounting bars.
6. Mounting Ring: 0.048" (18-ga.) galvanized steel. Designed for vertical
adjustment from above or below for ceilings from 0" to 2" thick. Center-line
notches allow consistent alignment of multiple fixtures.
7. Retention Springs: Rust resistant springs secure cone in place for quick,
tool-less installation.
8. Frame Vertical Adjustment Mechanism: Vertical adjustment mechanism
accommodates mounting to virtually any ceiling system using pre-installed
mounting bars, or 1/2" EMT tubing (by others). Single locking feature secures
all adjustments. Alignment holes and markings allow fixture to be pre-set
prior to installation.
9. Mounting Bars: 0.048" (18-ga.) Pre-installed, telescoping bars extend to 30"
long and lock securely into position. Built-in locking tabs provide positive attach-
ment to common T-bar systems. Self-centering feature simplifies installation in
24" O.C. grid systems. Attaches to steel or wood joists without accessories.
10.Ballast: Electronic 120V or 277V. Magnetic dual voltage (120V & 277V).
Accessible from below for inspection and/or replacement without tools.
11.Junction Box: 0.048" (18-ga.) galvanized steel. UL listed for 8 No. 12 AWG,
90°C through branch circuit conductors; allows inspection from below.
12.Thermal Protector: (Not Shown) Meets NEC and UL requirements. Do not
install insulation above nor within 3" (76mm) of any part of the luminaire.
Electrical
Electronic Ballast: 120V or 277V, 50/60 Hz., encased, high-power factor, T.H.D.
<15%, thermally and transient protected, RMI / RFI complies with FCC Part 18
non-consumer equipment, shut-down circuit at end of lamp life, sound rating  "A",
-5°F minimum starting temperature, Type 1 outdoor rating.
Electrical (cont)
Ballast
ANSI Code
Voltage
Max. Amps
Input Watts
70W MH
M98/M143
120/277
0.67/0.28 
78
100W MH M90/M140
120/277
0.90/0.43
110
Magnetic Ballast: 120/277V dual voltage, 60 Hz., encased and potted, 
HX-HPF circuit type, high power factor, sound rating “B”, -20°F minimum starting 
temperature, Type 1 Outdoor rating.
Ballast
ANSI Code
Voltage
Max. Amps
Input Watts
70W MH
M98/M143
120/277
1.90/0.80
94
100W MH M90/M140
120/277
2.40/1.10
125
Options and Accessories
Auxiliary: Add suffix to Frame-In Kit and Reflector Trim. See Spec.Sheet ”A“.
Emergency Lamp: Add suffix to Reflector Trim and Frame In Kit. See
Spec.Sheet “E”.
Slope Ceiling Adapters: See Specification Sheet SCA. 
Fuse (magnetic ballast): Add suffix F1 or F2 to Frame In Kit (F1=120V, F2=277V)
Chicago Plenum: Consult Factory.
Labels
UL (Suitable for Damp Locations), CSA (magnetic ballast only), I.B.E.W.
For 100W electronic, install fixtures with minimum spacing:  2 feet from 
center-to-center of adjacent luminaries; 1/2 inch from top of luminaire to over-
head building member; 1 foot from luminaire center to side building member.