Contec DIO-4 Manual Do Utilizador

Página de 4
 
 
Ver.1.00
 
  DIO-4/4(FIT)GY 
 
 
1
 
 
F&eIT Series 
Isolated Digital I/O Module 
 
DIO-4/4(FIT)GY 
 
 
 
*
 Specifications, color and design of the products are subject to 
change without notice. 
 
 
 
 
 
 
This product is an expansion module (device module) that adds 
digital signal I/O interfaces to one of various types of controllers.   
The product is used in combination with the I/O controller 
module <CPU-CAxx(FIT)GY> (*1) or microcontroller unit 
<CPU-SBxx(FIT)GY> (*1) in the F&eIT Series. 
This product can perform a maximum of 4 points of 
Optocoupler isolated input and 4 points of Optocoupler isolated 
output per module.    (Input: 12 - 24 VDC specified, output: 12 - 
48 VDC specified) 
*1   This module is available in different product models.  "x" in each model number 
represents a blank or one alphanumeric character.    This is applicable to the rest of this 
document. 
 
 
 
This product can perform 4-point digital signal input and 4-point 
digital signal output, treating 4 points as a group. 
Input section is ready to accept both the current sinking output 
and current source output. 
The output section is a high sink current, open collector type 
using high-capacitance transistors. 
    150 mA/24 VDC or 50 mA/48 VDC max. (per channel) 
Isolated I/O operations using an optocoupler improves noise 
immunity. 
A rotary switch allows you to set device IDs, making it easy to 
keep track of device numbers. 
Like other F&eIT series products, the module has a 35mm DIN 
rail mounting mechanism as standard.  A connection to a 
controller module can be effected on a lateral, stack basis in a 
unique configuration, which permits a simple, smart system 
configuration without the need for a backplane board. 
 
 
 
 
 
 
 
 
Module[DIO-4/4(FIT)GY] …1 
First step guide … 1 
CD-ROM [F&eIT Series Setup Disk] *1…1 
Interface connector plug…1 
 
*1    The CD-ROM contains various software and User’s Guide. 
 
Specifications 
Specifications 
Item 
DIO-4/4(FIT)GY 
Input section 
Input format 
Optocoupler isolated input   
(compatible with current sink output and current source 
output) 
Input resistance 
3k
Ω 
Input ON current 
3.4mA or more 
Input OFF current 
0.16mA or less 
Number of input signal points 4 points (4 points/common) 
Response time   
Within 1msec 
External circuit power supply
12 - 24VDC (±15%) 
(4mA/12V - 8mA/24V per channel) 
Output section 
Output format 
Optocoupler isolated open collector output (current sink type)
Output voltage 
12 - 48VDC (±15%)   
Ratings 
Output current 
150mA (12 - 24V) (per channel) (Max.) 
50mA (36 - 48V) (per channel) (Max.) 
Number of output signal 
points  
4 points (4 points/common) 
Response time   
Within 1msec 
External circuit power supply
12 - 48VDC (±15%) 
Common section 
Interrupt level 
Using CPU-SBxx(FIT)GY: IRQ 5, 7, or 9 
Internal current consumption
5VDC(±5%) 150mA(Max.) *1 
Allowable distance of signal 
extension 
Approx. 50m (depending on wiring environment) 
Physical dimensions (mm) 
25.2(W) x 64.7(D) x 94.0(H) (exclusive of protrusions) 
Weight of the module itself 
100g 
Module connection method 
Stack connection by means of a connection mechanism 
standard with the system. 
Module installation method 
One-touch connection to 35mm DIN rails   
(standard connection mechanism provided in the system) 
Applicable wire 
AWG 28 - 16    wire type: 0.32 - 1.30mm 
Applicable plug 
FRONT-MC 1,5/12-STF-3,81 (made by Phoenix Contact 
Corp.) 
3.81mm-pitch, rated current: 8A (Max.) 
*1    The stack connector accepts currents of up to 3.0A (Max.). 
 
Installation Environment Requirements 
Item Requirement 
description 
Operating temperature   
0 - 50
°C 
Storage temperature   
-10 - 60
°C 
Operating humidity 
10 - 90%RH (No condensation) 
Floating dust particles 
Not to be excessive 
Corrosive gases 
None 
Line-noise 
*1 
AC line/2kV, Signal line/1kV 
(IEC1000-4-4Level 3, EN61000-4-4Level 3) 
Noise immunity
Static 
electricity 
resistance
Contact discharge/4kV (IEC1000-4-2Level 2, 
EN61000-4-2Level 2) 
Atmospheric discharge/8kV (IEC1000-4-2Level 3, 
EN61000-4-2Level 3) 
Vibration 
resistance 
Sweep 
resistance
10 - 57Hz/semi-amplitude 0.15mm, 57 - 150Hz/2.0G 
80minutes each in X, Y, and Z directions 
(JIS C0040-compliant, IEC68-2-6-compliant) 
Impact resistance 
15G  half-sine shock for 11ms in X, Y, and Z directions   
(JIS C0041-compliant, IEC68-2-27-compliant) 
*1    When using a POW-AD22GY 
 
Specification  
Features  
 
 
Packing List