2. Water-Cooled Condenser
a) KML-250/351/451MWH
(1) Connection to an Open Drain System
Condenser Water 
Supply Inlet 
Minimum Condenser 
Water Supply Line Size 
Condenser Drain 
Outlet
Minimum Condenser 
Drain Line Size
1/2" Female Pipe 
Thread (FPT)
1/4" Nominal ID Copper 
Water Tubing or Equivalent
3/8" Female Pipe 
Thread (FPT)
1/4" Nominal ID Hard Pipe 
or Equivalent
• A condenser water supply line shut-off valve and drain valve must be installed.
• In some areas, a back flow preventer may be required in the cooling water circuit.
• In order to maintain the proper high side pressure, the condenser water supply inlet 
temperature should not drop below 45°F (7°C) and the condenser drain outlet temperature 
must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker installation 
is complete, confirm the condenser drain outlet temperature 5 minutes after a freeze 
cycle starts. If the condenser drain outlet temperature is not in the proper range, use a 
flat blade screwdriver to rotate the adjustment screw on the water-regulating valve until 
the temperature is in the proper range (rotate counterclockwise to raise temperature or 
clockwise to lower temperature).
Fig. 5
Water-Cooled Models
Connection to an Open Drain System
Model Shown: 
KML-451MWH
Icemaker
Icemaker Water 
Supply Inlet
1/2" FPT
Bin Drain Outlet
3/4" FPT
2-inch (5-cm) air gap
Floor Drain
Icemaker
Drain Outlet 
3/4" FPT
Vent Tube
Vent Tube
Minimum 1/4" 
Nominal ID 
Hard Pipe or 
Equivalent
Condenser Water 
Supply Inlet
1/2" FPT
Condenser 
Drain Outlet 
3/8" FPT
Shut-Off Valve
Minimum 1/4" Nominal ID Copper 
Water Tubing or Equivalent
Drain Valve
Ice 
Storage 
Bin
Minimum 3/4" Nominal ID 
Hard Pipe or Equivalent
Separate piping to approved 
drain. Leave a 2-inch (5-cm) 
vertical air gap between the 
end of each pipe and the 
drain.
Be sure there is sufficient 
extra water supply line and 
drain line for the appliance 
to be pulled out for service.