SERVICING
47
Model
Switch 5
Switch 6
CFM
OFF
OFF
1,200
ON
OFF
1,000
OFF
ON
800
ON
ON
600
OFF
OFF
1,600
ON
OFF
1,400
OFF
ON
1,200
ON
ON
1,000
OFF
OFF
2,000
ON
OFF
1,800
OFF
ON
1,600
ON
ON
1,200
MBE1200
MBE1600
MBE2000
Cooling/Heat Pump Operation
Table 3
THERMOSTAT “FAN ONLY” MODE
During Fan Only Operations, the CFM output is 30% of the
cooling setting.
CFM TRIM ADJUST
Minor adjustments can be made through the dip switch
combination of 7-8.  Table 4 shows the switch position for
this feature.
NOTE:  The airflow will not make the decreasing adjustment
in Electric Heat mode.
C FM
S w it c h   7
S w it c h   8
+ 1 0 %
O N
O F F
- 1 5 %
O F F
O N
Table 4
HUMIDITY CONTROL
When using a Humidstat (normally closed), cut jumper PJ6
on the control board. The Humidstat will only affect cooling
airflow by adjusting the Airflow to 85%.
TWO STAGE HEATING
When using staged electric heat, cut jumper PJ4 on the
control board.
AEPF DIPSWITCH FUNCTIONS
Dipswitch 1/2 & 7/8
AEPF 1830
Heating
Element
(kw)
1
2
7
8
UP TO 10
OFF
OFF
OFF
OFF
1100
1210
UP TO 10
ON
OFF
OFF
OFF
890
935
5
OFF
ON
OFF
OFF
700
770
AEPF3036 / 3137 / 4260
Heating
Element
(kw)
1
2
7
8
UP TO 20
OFF
OFF
OFF
OFF
2050
2150
UP TO 20
ON
OFF
OFF
OFF
1750
1835
UP TO 15
OFF
ON
OFF
OFF
1600
1680
UP TO 10
ON
ON
OFF
OFF
1200
1260
UP TO 10
ON
ON
OFF
ON
1020
1070
Heat Pump
With Backup
Switch
Position
Switch
Position
Switch
Position
Switch
Position
Emergency
Backup
Heat Pump
With Backup
Emergency
Backup
Dipswitch 5/6 & 7/8
AEPF 1830
5
6
7
8
Cooling
Heat  Pump
OFF
OFF
OFF
OFF
1100
1100
ON
OFF
OFF
OFF
800
800
OFF
ON
OFF
OFF
600
600
5
6
7
8
Cooling
Heat  Pump
OFF
OFF
OFF
OFF
1800
1800
ON
OFF
OFF
OFF
1580
1580
OFF
ON
OFF
OFF
1480
1480
ON
ON
OFF
OFF
1200
1200
ON
ON
OFF
ON
1020
1020
Switch
Position
Switch
Position
Indoor Airflow
Switch
Position
Switch
Position
Indoor Airflow
AEPF3036 /  3137  / 4260