Sterling 882.93092.01 Manual Do Utilizador

Página de 90
GP Series Portable Chillers 
Chapter 4: Operation 
43 of 90 
Variable 
Description 
Access Level 
Operator 
Supervisor 
Tank Max Lvl 
Maximum tank level.  Used to set the default high 
tank level alarm setpoints as well as the auto-water 
makeup off setpoint. 
 
x
 
Low Level Fault 
Tank level that will activate Low Level Warning 
fault 
 
x
 
Low Level Warning 
Tank level that will activate Low Level Warning 
alarm 
 
x
 
Wtr Makeup On 
The tank level to turn on optional water make-up 
valve; based on size of tank 
 
x
 
Wtr Makeup Off 
The tank level to turn off optional water make-up 
valve; based on size of tank. 
 
x
 
High Lvl Warning 
Tank level that will activate High Level Warning 
alarm 
 
x
 
High Lvl Fault 
Tank level that will activate High Level Warning 
fault 
 
Mkup Min Rt X.X”/XXS 
The minimum allowable rate for filling the tank 
 
Operator Password 
4 digit password to limit operator interaction 
 
Operator Pw Time 
Time in minutes for operator password to be active 
 
Sprvisor Password 
4 digit password for supervisory interaction 
 
Sprvisor Pw Time 
Time in minutes for supervisor password to be active 
 
Alarm Silence Time 
Time in minutes to silence alarm (with optional 
audible alarm).  After time alarm will reactivate. 
 
Set Clock 
Allows for the time to be set if the clock card option 
is installed 
 
Reset to Defaults 
Resets all parameters to the default parameters, 
including configuration 
 
 
1.  Set the Leaving Fluid temperature by depressing the 
 button to display 
the menu. 
 
Figure 17: Menu Screen 
2.  Depress the 
 or 
 button to highlight SETTINGS and press 
.  If 
passwords were setup (See Section 3-12 for information on the controller 
passwords) the password screen will appear.