GP Series Portable Chillers 
Chapter 7: Appendix 
74 of 90 
 
Pure Water at >40°F 
 
GPXC-20 
GPXC-30 
GPXC-40 
GPXC-50 
 
GPM 
DP (PSI) 
GPM 
DP (PSI) 
GPM 
DP (PSI) 
GPM 
DP (PSI) 
0.5X Nominal 
1.7 
1.7 
12 
1.6 
18 
1.8 
1.0X Nominal 
12 
5.9 
18 
6.1 
24 
5.8 
36 
6.4 
2.0X Nominal 
24 
21.4 
36 
21.9 
48 
20.7 
72 
23.3 
 
 
 
 
 
 
 
 
 
 
GPXC-70 
GPXC-90 
GPXC-140 
GPXC-175 
0.5X Nominal 
24 
1.7 
30 
1.8 
36 
1.7 
48 
1.8 
1.0X Nominal 
48 
6.1 
60 
6.5 
72 
6.1 
96 
6.4 
2.0X Nominal 
96 
21.9 
120 
23.5 
144 
22.1 
192 
23.6 
 
 
 
 
 
 
 
 
 
 
GPXC-210 
 
 
 
 
 
 
0.5X Nominal 
72 
1.7 
 
 
 
 
 
 
1.0X Nominal 
144 
6.2 
 
 
 
 
 
 
2.0X Nominal 
288 
22.7 
 
 
 
 
 
 
 
Calculating Chiller Nominal Flow and Pressure to Process 

  Flow rate: Obtain the flow reading from the appropriate pump curve. 

  Pressure: Obtain a corresponding pressure reading from the pump curve you selected, 
then subtract the one-pump pressure drop listed in the above table using the 
appropriate chiller hp and flow rate.