Chapter 2: Functional Description 
10 of 44 
High Pressure Cutout 
This electro-mechanical cutout device opens the compressor control circuit if the refrigeration 
system compressor discharge pressure exceeds 575 psi..  
Note: 
The high-pressure cutout is a manual reset device typically mounted on the 
compressor discharge line inside the mechanical cabinet. Call a refrigeration 
service technician to analyze the problem and reset the control.  
Low Pressure Cutout (no switch but done through the transducer) 
This electro-mechanical cutout device opens the compressor control circuit if refrigeration 
system compressor suction pressure drops below 15 psi. It automatically resets when 
refrigerant suction pressure reaches 30 psi. 
Note: 
The low pressure cutout is an automatic reset device typically mounted on the 
compressor suction line inside the mechanical cabinet. Call a refrigeration 
service technician to analyze the problem and reset the control. 
Flow Switch  
The thermal dispersion flow switch cutout device, mounted in the process piping, shuts down 
the chiller if it senses that the water/glycol flow rate through the evaporator has dropped 
below an acceptable level. The flow switch opens the control circuit and shuts down the 
pumps and the chiller. 
Remote Start/Stop Interlock 
An additional contact is provided to allow the remote starting or stopping of the chiller. To 
use this feature, remove the jumper between terminals X1 and 1, and supply a switch or dry 
contact interlock connected in series between these two terminals. Refer to the schematic 
inside the control enclosure door.
 
 
2-5 Optional 
Features 
Options marked with “*” indicate options that can be factory installed or retrofitted in the 
field.  
Automatic Water Make-Up*. Not available on chillers less reservoir tank. Includes an 
electric water solenoid valve, a level sensing pressure switch mounted in the reservoir tank, 
and the necessary internal piping to connect the chiller to a make-up water source.  See 
Appendix for typical piping diagrams. 
Caution!  Customer piping must provide backflow protection and venting of tank to 
atmosphere to prevent over-pressurization of the reservoir tank (not needed for 
open tank). See 
Error! Reference source not found. on page Error! Bookmark 
not defined.
Process Water Sidestream Filter*. Not available on chillers less pump and reservoir tank. 
Includes a 50 micron filter, flow meter, ball valve for throttling water flow, and the necessary 
piping to provide constant filtering of the process water at about one gallon per minute (1 
gpm/3.8lpm). 
General Fault Indicator Audible/Visual Alarm*. Includes a 100 dB audible alarm horn/ 
visual alarm strobe and silence button with provisions for customer wiring indication