Chapter 4: Operation 
28 of 44 
4-5 Controller 
Setpoints 
 
Access Level 
Variable Description 
Operator Supervisor 
Leaving Temp 
Temperature of fluid out to process 
Hi Temp Warning 
Setpoint for alarm to warn when leaving fluid 
temperature is too high 
x x 
Hi Temp Fault 
Setpoint to shut down pump and compressor based on 
leaving fluid temperature 
x x 
Compressor On 
Differential 
Temperature Difference between Leaving Fluid 
Temperature and Setpoint to turn on the compressor 
 x 
Compressor Off 
Differential 
Temperature Difference between Leaving Fluid 
Temperature and Setpoint to turn off the compressor 
 x 
Pump Stop Delay 
Delay time in seconds between fault and stopping the 
pump 
 x 
Low Temperature 
Warning 
Temperature to activate Low Temperature Warning 
alarm 
 x 
Low Temperature Fault 
Temperature to activate Low Temperature Fault alarm 
 
Water Make-up On 
The tank level to turn on optional water make-up valve; 
based on size of tank 
 x 
Water Make-up Off 
The tank level to turn off optional water make-up valve; 
based on size of tank. 
 x 
Water Make-up Time 
The time in seconds that controller will allow for filling 
the tank 
 x 
Low Level Warning 
Tank level that will activate Low Level Warning alarm 
 
Low Level Fault 
Tank level that will activate Low Level Warning fault 
 
High Level Warning 
Tank level that will activate High Level Warning alarm 
 
High Level Fault 
Tank level that will activate High Level Warning fault 
 
High Temperature 
Delay 
Delay time in minutes between fault and stopping the 
compressor and pump 
 x 
Alarm Silence Time 
Time in minutes to silence alarm (with optional audible 
alarm).  After time alarm will reactivate. 
 x 
Operator Password 
Time 
Time in minutes for operator password to be active 
 
Supervisor Password 
Time 
Time in minutes for supervisor password to be active