SERVICE INSTRUCTIONS 
 
1.  High head pressure and high back pressure: 
A.  Condenser coil clogged or restricted 
B.  Condenser fan motor defective. 
C.  Air discharge in rear of cabinet restricted. 
2.  Low back pressure and low head pressure:                                       
A.  Restriction in system. 
B.  Refrigerant undercharged. 
C.  Leak in system 
3.  Pressure normal – cabinet warm: 
A.  Coil blocked with frost (see #4). 
B.  Refrigerant undercharged. 
C.  Control set too warm. 
4.  Cabinet not cycling – coil blocked with frost: 
A.  Defective temperature controller. 
B.  Refrigerant overcharged. 
C.  Location too hot. 
D.  Condenser clogged. 
E.  Condenser fan motor defective. 
5.  Compressor starts and runs – but cycles on overload: 
A.  Low voltage 
B.  Relay defective. 
C.  Overload defective. 
D.  High head pressure (see #1).