If the address assignments placed into the LAG ADDRESS and STANDBY ADDRESS 
values conflict, the lead/lag will be disabled and an alert (!) message will occur. For example, if 
the LAG ADDRESS matches the lead machine’s address, the lead/lag will be disabled and an 
alert (!) message will occur. The lead/lag maintenance screen (MAINT04) will display the 
message ‘INVALID CONFIG’ in the LEAD/LAG CONFIGURATION and CURRENT MODE 
fields. 
The lead chiller responds to normal start/stop controls such as occupancy schedule, forced 
start/stop, and remote start contact inputs. After completing start up and ramp loading, the PIC 
evaluates the need for additional capacity. If additional capacity is needed, the PIC initiates the 
start up of the chiller configured at the LAG ADDRESS. If the lag chiller is faulted (in alarm) or is 
in the OFF or LOCAL modes, then the chiller at the STANDBY ADDRESS (if configured) is 
requested to start. After the second chiller is started and is running, the lead chiller shall monitor 
conditions and evaluate whether the capacity has reduced enough for the lead chiller to sustain 
the system alone. If the capacity is reduced enough for the lead chiller to sustain the CONTROL 
POINT temperatures alone, then the operating lag chiller is stopped. 
If the lead chiller is stopped in CCN mode for any reason other than an alarm (*) condition, 
then the lag and standby chillers are stopped. If the configured lead chiller stops for and alarm 
condition, then the configured lag chiller takes the lead chiller’s place as the lead chiller and the 
standby chiller serves as the lag chiller.