RS-485 Communications
RS-485 COMMUNICATIONS
Daisy-chaining Devices to the Power Meter 
The RS-485 slave port allows the power meter to be connected in a daisy chain 
with up to 63 2-wire devices. In this bulletin, communications link refers to a 
chain of devices that are connected by a communications cable.
Figure 7  Daisy-chaining multiple devices
+
S
Belden 1120 A or equivalent (600 V)
120 Ω terminator 
on the first and 
last device of the 
daisy chain
Shield wire
•  The terminal’s voltage and current ratings are compliant with the 
requirements of the EIA RS-485 communications standard.
•  The RS-485 transceivers are ¼ unit load or less.
•  RS-485+ has a 47 kΩ pull up to +5V, and RS-485- has a 47 kΩ pull 
down to Shield (RS-485 signal ground).
•  Wire the RS-485 bus as a daisy chain from device to device, without 
any stubs. Use 120 Ω termination resistors at each end of the bus (not 
included). 
•  Shield is not internally connected to Earth Ground.
•  Connect Shield to Earth Ground somewhere on the RS-485 bus.
•  Use 14-24 gauge wire for all connections.
•  When tightening terminals, ensure that the correct torque is applied: 
3.5 - 4.4 in·lb (0.4-0.5 N·m).
Figure 8  Torque requirements
+
S
Red
Black
 
Gray
 
3.5–4.4 in•lb
(0.4–0.5 N•m)
Use 14-24 gauge wire