Table 41. DC power supply and fan unit LEDs
Number
LED
Normal Status
Problem Status
1
1
DC power supply and fan
unit power
On
Off
2
Service Action Allowed
(OK to Remove)
Off
On
2
3
Service Action Required
(Fault)
Off
On
2
4
1
Direct Current Enabled
On
Off
Notes:
1. Although the symbols for dc power supply and fan unit power and Direct Current Enabled
LEDs are the same, the LEDs serve different purposes. The dc power supply and fan unit
power LED indicates that dc inputs to the dc power supply and fan unit are present and
good. The Direct Current Enabled LED indicates that the dc output from the dc power
supply and fan unit to the internal circuitry is good.
2. Verify that any attached disconnect device is set to On and the power switch is in the On
position when these LEDs are lit. If the disconnect device switch is at the On position, flip
it to the Off position, wait at least 15 seconds and flip it again to the On position. If these
LEDs did not change to an unlit state in 30 seconds, replace the dc power supply and fan
unit CRU.
Front LEDs
This section describes the primary LEDs and controls on the front of the storage
subsystem for all models.
ds470086
2
3
4
1
1
2
3
4
Figure 97. DC power supply and fan unit LEDs
Chapter 4. Operating the storage subsystem
127