3.7 System monitoring 
M200D AS-Interface Basic 
Manual, 03/2009, A5E01668085-01 
31
 
3.7.2 
Asymmetry monitoring 
Description   
Three-phase induction motors respond to slight asymmetries in the supply voltage with a 
higher asymmetric current consumption, which causes the temperature in the stator and 
rotor windings to increase. In this case, the M200D motor starter protects the motor against 
overload by shutting it down. 
 
 
Note 
When the motor is switched on, asymmetry evaluation is suppressed for approx. 0.5 s. 
 
Asymmetry limit value   
The asymmetry limit is a percentage value by which the motor current is allowed to deviate 
in each phase.  
Asymmetry occurs when the difference between the lowest and highest phase current is 
greater than the asymmetry limit value. The asymmetry limit for the M200D AS-i Basic is set 
permanently to 30 %.  
The reference value for the evaluation is the maximum phase current in one of the 3 phases. 
Response to asymmetry 
If the asymmetry limit value is exceeded, the motor starter is shut down.