Siemens M200D Manual Do Utilizador
M200D AS-Interface Basic
Manual, 03/2009, A5E01668085-01
Manual, 03/2009, A5E01668085-01
89
Technical specifications
8
8.1
General technical specifications
Location
In the plant
Wall mounted (near motor)
Permissible mounting
positions
Vertical, horizontal, flat
Degree of protection
IP65
Waterproof to IEC 529 (DIN 40050)
Protection class
1
IEC 60364-4-41 (DIN VDE 0100-410)
Touch protection
Finger-safe
Degree of pollution
3
To IEC 60664
Cooling
Convection
No additional cooling required
Operating temperature
–25°C to + 40°C
max. 55°C
With reduction of I
e
(see "Derating")
Transport and storage
temperature
–40°C to + 70°C
—
Air humidity
10 % to 95 %
Condensation must not be allowed to form
Max. temperature change
1 K / min
IEC 60068, Part 2-14
Chemical environment
conditions
3C3
conforming to IEC 60721-3-3
Installation altitude
1000 m
2000 m
No restrictions
With restrictions (reduction of I
e
by 1 % every
100 m up to 2000 m)
Vibration resistance
2 g
To IEC 60 068, Part 2-6
Shock
12 g with 11 ms
without influencing point of contact:
9.8 g / 5 ms or 5.9 g / 10 ms
To IEC 60 068, Part 2-27
half-sine
Free fall
0.6 m
In product packaging
ESD
8 kV air discharge
4 kV contact discharge
IEC 61000-4-2
Severity grade 3
Electromagnetic fields
10 V/m
IEC 61000-4-3
Severity grade 3
BURST
2 kV / 5 kHz supply voltage
2 kV / 5 kHz data cables
2 kV / 5 kHz process cables
IEC 61000-4-4
Severity grade 3
SURGE
Installation class 1 to 3
1)
1 / 2 kV
IEC 61000-4-5
Severity grade 3
Emitted interference
Limit value class A
EN 55011
1)
If the starter is used in installation class 3 (increased overvoltage due to parallel cable installation), an overvoltage
protection module (3RK1901-1GA00 and 3RG9030-0AA00) must be used.