Schneider Electric Altivar 12 Manual Do Utilizador

Página de 133
BBV28581  05/2010
51
Code
Name/Description
Adjustment range
Factory setting
I_O-
Input Output menu 
(continued)
tCt
2 wire type control
trn
LEL
trn
PFO
DANGER
UNINTENDED EQUIPMENT OPERATION
Check that the modification of the 2 wire type control is compatible with the wiring diagram used.
Failure to follow these instructions will result in death or serious injury.
2-wire type control parameter can only be accessed if 
Type of control
 tCC
 is set to 
2C
.
v
Level: State 0 or 1 is taken into account for run or stop.
v
Transition: A change of state (transition or edge) is necessary to initiate operation, to help prevent 
accidental restarts after a power supply interruption.
v
Priority FW: State 0 or 1 is taken into account for run or stop, but the "forward" input takes priority over 
the "reverse" input.
nPL
Logic inputs type
POS
POS
nEG
EnEG
v
Positive: the inputs are active (state 1) at a voltage equal to or higher than 11 V (for example +24 V 
terminal). They are inactive (state 0) when the drive is disconnected or at a voltage lower than 5 V.
v
Negative using internal supply: the inputs are active (state 1) at a voltage lower than 10 V (for example 
COM terminal). They are inactive (state 0) at a voltage equal to or higher than 16 V or when the drive is 
disconnected.
v
Negative using external supply : the inputs are active (state 1) at a voltage lower than 10 V (for example 
COM terminal). They are inactive (state 0) at a voltage equal to or higher than 16 V.
Note: The modification will be taken into account only at the next control power on.
25.
I-O-
drC-
CtL-
FUN-
FLt-
COM-