TROUBLESHOOTING
Note:
 Before troubleshooting the system, make sure the gas shutoff valve is ON.
The two most common causes of a malfunctioning gas appliance are:
1. Loose wiring connections
2. Construction debris clogging the pilot and/or gas control valve filter
OBSERVED PROBLEM
Pilot will not light
Pilot will not stay lit
No gas to burner, although wall switch and 
valve are set to the ON position
Frequent pilot outage
Pilot goes out when wall switch is ON
POSSIBLE CAUSE
1.  No gas supply or shutoff valve is OFF
2.  Air in gas line
3.  Construction  debris  clogging  pilot 
orifice
4.  Low gas pressure
5.  Control valve knob is not on the PILOT 
position
6.  Kinked pilot line
7.  Bad valve
8.  Vent damper not fully open
1.  Loose wiring on thermopile to regulator 
valve. No millivolt current is being sent 
back to regulator
2.  If valve knob and wall switch are in the 
ON position, probable defective regula-
tor valve
3.  Vent damper not fully open
1.  Wall switch wires defective or too long
2.  Thermopile  not  generating  sufficient 
voltage
1.  Pilot  flame  may  be  too  low,  causing 
safety pilot to “drop out”
2.  Improper venting or excessive blockage
1.  Millivolt  output  on  thermopile  too 
high
REMEDY
1.  Check to see if you have gas supply
2.  Hold regulator control valve in the PI-
LOT position for 2 to 3 minutes to purge 
air. If you smell gas stop and wait for a 
few minutes before trying to light the 
fireplace
3.  Remove  debris  and  dirt,  inspect  and 
clean any other possible obstructions
4.  Contact your gas supplier
5.  Refer to section on pilot lighting
6.  Have  a  qualified  technician  replace 
pilot line
7.  Replace regulator valve (see Accesso-
ries, page 27)
8.  Open vent damper until fully locked in 
OPEN position 
1.  Check  wiring  connections.  Refer  to 
wiring diagram shown in Wall Switch 
Installation, page 10
2.  Have  a  qualified  technician  replace 
valve
3.  Open vent damper until fully locked in 
OPEN position
1.  Check electrical connections
2.  See Pilot will not stay lit, above
1.  Clean and adjust pilot flame for maxi-
mum  flame  impingement  on  thermo-
pile
2.  Have the vent system inspected, includ-
ing the termination cap. Remove any 
restriction or obstruction
1.  Replace thermopile