Teledyne powerpod 400 Manual Do Utilizador

Página de 42
164-122012 Power
P
OD
 400
 
Page 28 of 42
 
 
10.9.  SERIAL COMMUNICATION 
Follow the instructions in the section, WIRING THE POWER
POD
-400 for cabling and proper pin out for 
serial communication with the unit.  After insuring that the POWER
POD
-400 is wired properly, the unit 
must be set up following the instructions in the section entitled, External Communications Setup.   
The instruction set for the POWER
POD
-400 can be divided into two different types.  They differ only in 
that they 
1.  Write a command only or 
2.  Write a command and read a response. 
 
Taking liberty with this vernacular, they may be differentiated using the terms COMMAND or QUERY.  
The entire set of instructions can be found in Appendix B. 
10.9.1.  Commands 
Typical RS-232 command structure is as follows:    CMNDn<value>Cr 
For example: To change channel three’s high alarm value to 75.00, send A3H075.00Cr. 
RS-485 commands require only that an asterisk and the unit’s address precede the RS-232 Command.  
Using the same example as above with a unit whose address is 10 (default), send *10A3H075.00Cr. 
When the POWER
POD
-400 is the terminating unit on a 485 bus, two jumpers, CJ1 and CJ2 can be 
shorted to add the required terminating resistors.  Remove two machine screws from the rear of the top 
cover.  Slide the cover off.  The two jumpers are near the serial communication connectors. 
10.9.2.  Set Point Queries 
Queries are used when information from the unit is required.  Each query is followed by a response from 
the POWERPOD-400. 
In this case, the query is asking for a programmed value.  Specifically, the set point of channel three, which 
happens to be set at 50.00 of 100.00. 
Sent   SP3Cr 
Response  
SP3  050.00 
10.9.3.  Alarm/Flag Queries 
The state of the high and low flow alarms for each channel can be monitored via the DB-15 connecter (J8) 
on the rear panel for immediate action from an alarm situation but the Totalizer set points can only be 
monitored by reading a memory location’s Boolean setting via serial communication.
 
As shown in the section, Setting Limit Alarms, to simply QUERY channel three’s high alarm set point, 
send A3HCr. Expect a response similar to A3H  075.00.  The actual state of the alarm can be polled using 
the STATUS query. 
STCr 
Which results in a response similar to 
STATUS 
OCA :  CH1 AUTO   CH2 CLOSED  CH3 OPEN  CH4 AUTO 
HI/LO:  0/0   0/1   1/0   0/0 
OCA is short for OPEN/CLOSED/AUTO. 
HI/LO stands for the high flow limit alarm or the low flow limit alarm.  One must parse the states if digital 
tests are to be conducted.