When the functions of the Lossnay unit were changed by function selection after installation, always indicate the set contents by entering   or 
other mark in the appropriate check field of the tables shown in page 7 and 8. (Settings may be lost if the remote controller malfunctions.)
When replacing a remote controller, specify the same settings as before the replacement.
NOTE
6.  Wiring hole for installing directly on the wall (or open wiring)
• Cut off the shaded area from the upper cover using a knife, nippers, etc.
• Take out the remote control cord connected to the terminal block via this portion.
7.  Install the cover to the remote controller.
First, hook the cover to the two upper claws and then fit it to the remote controller.
 CAUTION Press the cover until it snaps shut. If not, it may fall off.
NOTE:  A protection sheet is stuck to the operation section. Peel off this protection sheet before use.
Operation
Relevant button
Relevant display items
Sequence
1. Starting the Lossnay unit
Operation lamp
“High” 
Press the [
 ON/OFF] button and confirm that the Operation lamp turns on. 
2. Setting the ventilation mode
“HEAT EX.” non-automatic
Press the Function selector button: Each time it is pressed, the corresponding display 
will change in accordance with the sequence [HEAT EX.] (non-automatic) --> [BY-
PASS] (non-automatic) --> [AUTO].
3. Selecting the fan speed
“Low”     “Extra High”
Press the Fan Speed Adjustment button to select either Low or High (Extra High) fan 
speed. High and Extra-High can be selectable by initial setting. 
4. Selecting the Extra Low fan 
speed*
1
*
2
“Extra Low”
Press the  “Extra Low” fan speed button. 
Extra low operation will begin. Pressing the Fan Speed Adjustment button will cause 
the fan speed to revert to its original speed (before the Extra low mode began). 
Pressing the Extra Low fan speed button again will return operation to Extra low mode.
5. Stopping the Lossnay unit
Operation lamp
Press the [
 ON/OFF] button.*
2
(Press the [
 ON/OFF] button to turn off the Operation lamp.)
*
1
  If you press a button for a feature that is not installed at the Lossnay unit, the remote controller will display the “NOT AVAILABLE” message. 
*
2
  If set to “24-hour Ventilation”, pressing the [
 ON/OFF] button will cause this to be displayed in the dot display “24HR VENTILATION”, and the operation will switch to 
Extra low fan speed mode. To stop operation, press the [
 ON/OFF] button twice within 3 seconds, or press and hold the [
 ON/OFF] button for 5 seconds.
If error code is displayed, refer to the following table.
Error code
Cause
Action
0900
The SW2 trial-operation switch from the Lossnay controll box 
is On.
Turn off the trial-operation switch.
6608
If two or more Lossnay units are used together, “6608” may 
indicate that the correct setting has not been performed using 
the main/sub switches.
Turn off the power supply and use the main/sub switches to 
specify one Lossnay unit as the main and the others as sub. 
Turn the  power supply back on. Note that all Lossnay units are 
specified as main before shipment from the manufacturing plant.
If two remote controllers are used together, “6608” may 
indicate that one of the controllers is not connected.
Turn off the power supply, connect the remote controller, then turn 
the power supply back on.
If two remote controllers are used together, “6608” 
may indicate that both of these controllers are not set 
automatically when the power is turned on.
Turn off the power supply, then turn it back on.
Multiple transmission cables are wired with multi core cables.
For the applied transmission cable, wire the transmission cables 
away from the other transmission cable.
Communication error (M-NET side)
Turn off the power supply and contact the distributor.
4116
A circuit error has occurred in the Lossnay unit.
3126
Temperature error (OA side).
5101
An error has occurred in the Lossnay thermistor (OA side).
5102
An error has occurred in the Lossnay thermistor (RA side).
3602
An error has occurred in the damper motor.
6600
Multiple address error (M-NET side)
6602
6603
6606
6607
Communication error (M-NET side)
1.  Choose a place in which to install the remote controller (switch box).
Be sure to observe the following steps:
(1)  When installing on either the switch box or the wall, allow extra space around the remote controller as 
shown in the figure at the right.
(2)  Parts which must be supplied on site.
• Switch box for two units
• Thin-copper wiring pipe
• Lock nut and bushing
• Surface raceways
Construction precautions
• Do not connect a wire exceeding the specified thickness to the terminal block. (This can lead to damage.)
• Do not run together with other wiring in a wiring conduit. (This can cause communication errors.)
• Do not connect multiple communication lines using a single multicore cable. (This can cause 
communication errors.)
• The total length of the communication line must be 500 m or less. (This can cause communication errors.)
2.  Seal the remote controller cord with putty in order to prevent the possible entry of dew, water droplets, cockroaches, other insects, etc.
When using the switch box
• When installing on the switch box, seal the 
connections between the switch box and wiring 
pipe with putty.
When installing directly on the wall
• When opening a hole using a drill for the remote controller cord (or when taking the cord out 
of the back of the remote controller), seal the hole with putty.
• When routing the cord via the portion cut off from the upper cover, similarly seal that portion 
with putty.
• When taking the remote controller cord from back of the controller, use surface raceways.
Lossnay Component for residential, 
commercial or light-industrial use
Lossnay Remote Controller 
PZ-60DR-E
Installation Manual
This instruction manual describes how to install the Lossnay unit.
Please read this manual thoroughly and install the remote controller accordingly. For information on how to wire and install the Lossnay units, refer to 
the Lossnay unit installation manual. After the installation, hand over this manual to users. 
 
Read these Safety Precautions and perform installation work accordingly.
 
The following two symbols are used to dangers that may be caused by incorrect use and their degree:
 WARNING
This symbol denotes what could lead to serious injury or death if you misuse the PZ-60DR-E.
 CAUTION
This symbol denotes what could lead to a personal injury or damage to your property if you misuse the PZ-60DR-E.
 
After reading this installation manual, give it and the indoor unit installation manual to the end user.
 
The end user should keep this manual and the indoor unit installation manual in a place where he or she can see it at anytime. 
 
When someone moves or repairs the PZ-60DR-E, make sure that this manual is forwarded to the end user.
Confirm that the box includes the following parts, in addition to this installation manual:
1.  Remote controller (cover, body) .........................................................................................1
2.  Cross recessed pan head screw (M4 × 30) .......................................................................2
3.  Wood screw (M4.1 × 16, used for directly hooking to the wall) ..........................................2
0809874HG8501A
GB
3.  Remove the remote controller cover.
• Insert a flathead screwdriver into one of the open slots and move the screwdriver in the arrow direction.
 CAUTION • Remove the cover carefully so as to avoid any damage.
• Do not turn the screwdriver in the slot. Doing so may 
damage the slot.
4.  Install the lower case on the switch box or directly on the wall.
When using the switch box
When installing directly on the wall
 CAUTION Do not tighten the screws too tight. Doing so may deform or crack the lower cover.
NOTE:  • Choose a flat plane for installation.
 
• Fasten the switch box at more than two places when installing directly on the wall.
 
• When reinstalling on the wall, fasten securely using anchors.
5.  Connect the remote control cord to the remote controller terminal block.
For the remote control, obtain a 2-core cable 
between 0.3 and 1.25 mm
2
 at the site.
 CAUTION Do not use crimp terminals to connect to remote controller terminal blocks. The terminals may contact the board and 
cause trouble or contact the cover and damage the cover.
 CAUTION Prevent remote cord chips from getting into the remote controller. Electric shock or malfunction may result.
Function selection of remote controller
The setting of the following remote controller functions can be changed using the remote controller function selection mode. Change the setting 
when needed.
Item 1
Item 2
Item 3 (Setting content)
[1] Change Language
(“CHANGE LANGUAGE”)
Language setting to display
Display in multiple languages is possible.
[2] Function limit
(“FUNCTION 
SELECTION”)
(1) Operation function limit setting (operation lock) 
(“LOCKING FUNCTION”)
Setting the range of operation limit (operation 
lock)
(2) 24-hour ventilation setting*
2
*
6
(“24HR VENTILATION”)
Sets whether the [
 ON/OFF] button stops 
operation completely or initiates Extra low 
operation.
[3] Mode selection
(“MODE SELECTION”)
(1) Use of clock setting*
3
 
(“CLOCK”)
Setting the use or non-use of clock function
(2) Timer function setting 
(“WEEKLY TIMER”)
Setting the timer type
(3) Contact number setting for error situation
(“CALL.”)
Contact number display in case of error
Setting the telephone number
[4] Display change
(“DISP MODE SETTING”)
(1) Filter cleaning setting
(“MAINTENANCE SIGN”)
(SW5-5)*
5
Set the schedule for “FILTER” indicator to appear 
after 3000-hour use, or no indication
(2) Lossnay cores cleaning setting
(“MAINTENANCE SIGN”)
Set the schedule for “CORE” indicator to appear 
after 6000-hour use, or no indication
[5] Installation settings*
1
*
2
(“LOSSNAY FUNCTION”)
(1) Supply fan speed setting 
(“SA SETTING”)
(SW2-4,9)*
5
Sets Extra High/High fan speed selection , and 
Multi Ventilation modes
(2) Exhaust fan speed setting 
(“EA SETTING”)
(SW2-5,10)*
5
Sets Extra High/High fan speed selection , and 
Multi Ventilation modes
(3) Power supply/exhaust when operation starts
(“POWER VENT START”)
(SW2-3)*
5
Switching to power supply/exhaust when 
operation starts
(4) Subordinate Lossnay settings*
(“
SUB
 SET”)
Enable/disable subordinate Lossnay unit supply 
and exhaust fan speed settings.
(5) Power supply ON/OFF/AUTO
(“RECOVERY SETTING”)
(SW2-6)*
5
(SW5-4)*
5
Controls stop and start operation by turning the 
power supply (220-240 V) for the Lossnay on 
and off.
(6) Operation monitor output selection
(“OPERATION MONITOR”)
(SW5-2)*
5
Sets whether the operation monitor will apply to 
the exhaust fan or the supply fan.
(7) Exhaust fan speed selection for cold region 
intermittent operation (“EA SETTING INTERMIT”)
(SW5-9)*
5
Sets exhaust fan speed for cold region 
intermittent operation.
(8) Night purge setting*
3
(“NIGHT PURGE”)
Enables/disables Night purge.
(9) Bypass automatic ventilation priority setting
(“BYPASS SETTING”)
(SW2-7)*
5
Selects the auto ventilation adjustment (AUTO) 
pattern.
[6] Interlocking settings*
1
*
2
(“INTERLOCK SETTING”)
(1) Interlock mode setting
(“INTERLOCK MODE”)
(SW5-7,8)*
5
These settings indicate how Lossnay should 
operate when external devices are started or 
stopped.
(2) Pulse input setting
(“INPUT SIGNAL”)
(SW2-2)*
5
Set when pulse signal equipment is connected to 
an external input.
(3) Delayed operation settings
(“DELAY OPERATION”)
(SW5-1)*
5
Setting for delay (of operation at startup of 
heating or cooling) 
(4) Exhaust operation settings for air conditioner 
defrosting (“EA SETTING DEFROST”)
(SW5-3)*
5
Stopping exhaust fan when defrosting air 
conditioner
[5] Installation settings and [6] Interlocking settings are selection modes that allow overriding of Lossnay unit Dip switches settings via remote 
controllers.
*
1
  When a remote controller is set to factory setting, the system operates according to the main unit Dip switch settings. When the remote controller settings are changed 
from the defaults, the system operates according to those settings. (The main unit switch settings are overridden.)
*
2
  If two remote controllers are used, these settings can be performed only for the “main” remote controller. These settings will be skipped for the “sub” remote controller 
and may not be modified. The designation of main and sub remote controller and are determined automatically upon main unit power-up. The remote controller for 
which [5] and [6] are displayed in the Function Selection mode is the main remote controller.
*
3
  Clock use must be set for Weekly timer and Night purge operation.
*
4
  Applies only to the following functions:
[Supply fan], [Exhaust fan], [Start up power supply and exhaust]
*
5
  Indicates Dip switches in the Lossnay control box.
*
6
  For the Lossnay models without those functions, those setting items will be nondisplay.
Dot display
The language that is selected 
in CHANGE LANGUAGE 
mode appears on this display. 
English is set in this manual.
[Function selection flowchart]
[1] Normal display 
(Display when the Lossnay unit is not running)
• If the remote controller Function Selection mode is entered during timer operation, the timer operation will be cancelled. Set timer operation after 
completing the remote controller Function Selection mode.
• When using two remote controllers, if one remote controller is set to remote controller Function Selection mode, “
” will be displayed in 
the other remote controller and its operation will be disabled.
• Button response may at times be slow due to communication processing; this is not a malfunction.
*
1
  For the Lossnay models without those functions, those setting items will be nondisplay.
*
2
  Those settings can be disabled depending on the other setting conditions.
*
3
  When two remote controllers are used, the settings will be displayed only in the main remote controller.
[1] Change Language
The language that appears on the dot display can be selected.
• Press the [
 MENU] button to change the language.
Japanese (
) (ja), English (en), German (de), Spanish (es), 
Russian (ru), Italian (it), Chinese (zh), French (fr)
[2] Function limit
(1)  Operation function limit setting (operation lock)
To switch the setting, press the [
 ON/OFF] button.
Dot display
Display
Function
Check
oFF
Operation lock setting is not made.
(Factory setting)
no1
Operation lock setting is made on all buttons 
other than the [
 ON/OFF] button.
no2
Operation lock setting is made on all 
buttons.
*  To make the operation lock setting valid on the normal screen, it is necessary to 
press buttons (Press and hold down the FILTER and [
 ON/OFF] buttons at 
the same time for 2 seconds.) on the normal display after the above setting is 
made.
*  The same operation is used to cancel the lock.
(2)  24-hour ventilation setting
Sets whether to stop operation completely or initiate Extra low 
operation by pressing the [
 ON/OFF] button during operation. 24-
hour Ventilation cannot be set when the pulse input setting is ON in 
the interlocking settings.
To switch the setting, press the [
 ON/OFF] button.
Dot display
Display
Function
Check
oFF
Pressing the [
 ON/OFF] button during 
operation stops operation. (Factory setting)
on
Pressing the [
 ON/OFF] button during 
operation initiates Extra low operation. 
Pressing the [
 ON/OFF] button twice 
within three seconds, or pressing and 
holding it for fi ve seconds, stops operation.
*  When 24-hour Ventilation is set to on, “24HR VENTILATION” will be displayed 
in the dot display during Extra low operation. The supply fan will stop and the 
exhaust fan will perform low notch operation if the system enters cold region 
intermittent mode during 24 hours operation.
*  For the Lossnay models without those functions, those setting items will be 
nondisplay.
[3] Mode selection
(1)  Use of clock setting
To switch the setting, press the [
 ON/OFF] button.
Dot display
Display
Function
Check
oFF
The clock function cannot be used.
on
The clock function can be used.
(Factory setting)
*  Set to ON to enable Weekly timer and Night purge.
(2)  Timer function setting
Selects whether to use a Weekly timer, Simple timer, or not to use 
any timer.
To switch the setting, press the [
 ON/OFF] button.
Dot display
Function
Check
The weekly timer can be used. (Factory setting)
When the use of clock setting is OFF, the “WEEKLY 
TIMER” cannot be used.
The simple timer can be used.
The timer mode cannot be used.
(3)  Contact number setting for error situation
To switch the setting, press the [
 ON/OFF] button.
Dot display
Function
Check
The set contact numbers are not displayed in case of 
error. (Factory setting)
The set contact numbers are displayed in case of 
error.
*  Setting the contact numbers
To set the contact numbers, follow the following procedures. 
Move the flashing cursor to set numbers. Press the OPERATION buttons to 
move the cursor to the right (left). Press the [
 CLOCK] buttons to set the 
numbers.
Pressing the CLEAR button will clear the set number.
[4] Display change 
(1)  Filter cleaning setting  
(SW5-5)
Set to OFF to disable Filter maintenance display.
To switch the setting, press the [
 ON/OFF] button.
Dot display
Display Other indicators
Function
Check
on
With maintenance sign 
(cumulative operation 
time : 3000 hours)* 
oFF
No maintenance sign
(Factory setting)
*  For Extra low fan speed, half of the actual operation time is added to the normal   
cumulative time.
(2)  Lossnay cores cleaning setting
Set to on to enable Lossnay core maintenance display.
To switch the setting, press the [
 ON/OFF] button.
Dot display
Display Other indicators
Function
Check
on
With maintenance sign 
(cumulative operation 
time: 6000 hours)*
oFF
No maintenance sign
(Factory setting)
*  For Extra low fan speed, half of the actual operation time is added to the normal   
cumulative time.
[5] Installation settings 
(1)  Supply fan speed setting 
(SW2-4,9)
Set supply to Extra High/High fan speed notch selection or Low 
fixed (multi ventilation mode).
To switch the setting, press the [
 ON/OFF] button.
Dot display
Display
Function
Check
SH : L
Used at “Extra High” and “Low” fan speed
H : L
Used at “High” and “Low” fan speed 
(Factory setting)
L
Fixed at “Low” fan speed (multi ventilation 
mode)
(2)  Exhaust fan speed setting 
(SW2-5,10)
Set exhaust to Extra High/High fan speed notch selection or Low 
fixed (multi ventilation mode).
To switch the setting, press the [
 ON/OFF] button.
Dot display
Display
Function
Check
SH : L
Used at “Extra High” and “Low” fan speed
H : L
Used at “High” and “Low” fan speed 
(Factory setting)
L
Fixed at “Low” fan speed (multi ventilation 
mode)
(3)  Power supply / exhaust when operation starts  
(SW2-3)
Set whether or not to perform power exhaust (30 minutes of fixed 
High (Extra High) fan speed) at start-up. When set to 24-hour 
Ventilation, pressing the [
 ON/OFF] button stops and re-starts 
operation.
To switch the setting, press the [
 ON/OFF] button.
Dot display
Display
Function
Check
oFF
Normal (Factory setting)
on
Power supply / exhaust is performed at 
start-up (After 30 minutes, the system 
switches to enable fan speed adjustment 
from the remote controller)
*  If power supply / exhaust is performed at start-up, the notch can be changed 
with the Fan speed Adjustment button.
(4)  Subordinate Lossnay settings 
Enables/disables usage of the supply and exhaust fan speed 
[ [5] (1) to (3) above] remote controller settings for the subordinate 
Lossnay. If set to “dIP”, only the main Lossnay will operate at the 
remote controller fan speed settings. The subordinate Lossnay will 
operate using the main unit Dip switch settings.
To switch the setting, press the [
 ON/OFF] button.
Dot display
Display
Function
Check
RC
Enables function settings for the 
subordinate Lossnay via the remote 
controller. (Factory setting)
dIP
Disables function settings for the 
subordinate Lossnay via the remote 
controller.
(5)  Power supply ON/OFF/AUTO 
 (SW2-6) (SW5-4)
Controls stop and start operation by turning the power supply (220-
240V) for the Lossnay on and off. 
To switch the setting, press the [
 ON/OFF] button.
Dot display
Display
Function
Check
oFF
Stop when the power is on 
(Factory setting)
on
Start when the power is on
AU o
Resume at the same operation mode (stop 
or start) before power off
(6)  Operation monitor output selection  
(SW5-2)
Selects whether the operation monitor output will apply to the 
exhaust fan (duing operation) or the supply fan.
To switch the setting, press the [
 ON/OFF] button.
Dot display
Display
Function
Check
1
Corresponds to opertation mode output 
exhaust fan (Factory setting)
2
Corresponds to operation mode output 
supply fan
(7)  Exhaust fan speed selection for cold region intermittent operation
 (SW5-9)
Selects the exhaust fan speed during cold region intermittent operation.
To switch the setting, press the [
 ON/OFF] button.
Dot display
Display
Function
Check
oFF
Exhaust fan stops.
Lo
Exhaust fan operates at “Low” (fi xed) fan 
speed. 
on
Exhaust fan operates normally (with no 
notch Change). (Factory setting)
(8) Night purge setting 
Night purge operation is used in the summer to automatically 
ventilate a room at night while the air conditioner is stopped, to 
discharge accumulated heat and thereby reduce the air conditioning 
load the next morning. Enables or disables Night purge operation.
To switch the setting, press the [
 ON/OFF] button.
Dot display
Display
Function
Check
oFF
Night purge mode is inactive. 
(Factory setting)
on
Night purge mode is active. 
*  See page 14 of the Operation Manual for details on Night purge.
*  Night purge cannot be used with the Simple timer.
(9)  Bypass automatic ventilation priority setting  
 (SW2-7)
Selects the auto ventilation adjustment (AUTO) pattern.
To switch the setting, press the [
 ON/OFF] button.
Dot display
Display
Function
Check
1
Normal (Factory setting)*
1
2
Outdoor air cooling priority mode*
2
*
1
  When the night purge is set by the remote controller, night purge operation 
starts at a temperature of 28°C (within 24 hours).
*
2
  When the night purge is set by the remote controller, night purge operation 
starts at a temperature of 17°C (within 24 hours).
[6] Interlocking settings 
(1)  Interlock mode setting  
 (SW5-7,8)
These settings indicate how Lossnay should operate when external 
devices are started or stopped.
To switch the setting, press the [
 ON/OFF] button.
Dot display
Display
Function
Check
onoF
ON/OFF interlock (Factory setting)
on
ON interlock
oFF
OFF interlock
oU *
External input given priority
*  External input signal priority cannot be set when the pulse input setting is on.
(2)  Pulse input setting  
 (SW2-2)
Set as shown when connecting the pulse signal equipment from a 
building maintenance system to an external input.
To switch the setting, press the [
 ON/OFF] button.
Dot display
Display
Function
Check
oFF
No pulse input (Factory setting)
on
Pulse input
*  24-hour Ventilation cannot be set when the pulse input setting is on.
(3)  Delayed operation settings   
 (SW5-1)
Selects whether or not to perform delayed operation when either an 
air conditioner or external equipment is running.
To switch the setting, press the [
 ON/OFF] button.
Dot display
Display
Function
Check
oFF
No operation delay (Factory setting)
on
Operation delay of 30 minutes
*  Delayed operation cannot be used when the pulse input setting is on.
(4)  Exhaust operation settings for air conditioner defrosting    (SW5-3)
Set the operation of the exhaust fan (with the air supply fan is 
stopped) during Mitsubishi air conditioner defrost mode when the 
Lossnay unit is connected to the air conditioner with a duct.
To switch the setting, press the [
 ON/OFF] button.
Dot display
Display
Function
Check
oFF
Stop
on
Operation (Factory setting)
 WARNING
Ask your dealer or technical representative to install the unit.
Any deficiency caused by your own installation may result in an electric shock 
or fire.
Install in a place which is strong enough to withstand the weight of the 
PZ-60DR-E.
Any lack of strength may cause the PZ-60DR-E to fall down, resulting in 
personal injury.
Firmly connect the wiring using the specified cables. Carefully check 
that the cables do not exert any force on the terminals.
Improper wiring connections may produce heat and possibly a fire.
Never modify or repair the PZ-60DR-E by yourself.
Any deficiency caused by your modification or repair may result in an electric 
shock or fire.
Consult with your dealer about repairs.
Ensure that installation work is done correctly following this installation 
manual.
Any deficiency caused by installation may result in an electric shock or fire.
All electrical work must be performed by a licensed technician, 
according to local regulations and the instructions given in this manual.
Any lack of electric circuit or any deficiency caused by installation may result 
in an electric shock or fire.
Do not move and re-install the PZ-60DR-E yourself.
Any deficiency caused by installation may result in an electric shock or fire.
Ask your distributor or special vendor for moving and installation.
To dispose of this product, consult your dealer.
 CAUTION
Do not install in any place exposed to flammable gas leakage.
Flammable gases accumulated around the body of PZ-60DR-E may cause 
an explosion.
Do not use in any special environment.
Using in any place exposed to oil (including machine oil), steam and sulfuric 
gas may deteriorate the performance significantly or give damage to the 
component parts.
When installing the remote controller in a hospital or communication 
facility, take ample countermeasures against noise.
Inverters, emergency power supply generators, high-frequency medical 
equipment, and wireless communication equipment can cause the remote 
controller to malfunction or to fail. Radiation from the remote controller may 
effect communication equipment and prevent medial operations on the 
human body or interfere with image transmission and cause noise.
Wire so that it does not receive any tension.
Tension may cause wire breakage, heating or fire.
Completely seal the wire lead-in port with putty etc. 
Any dew, moisture, insects entering the unit may cause an electric shock or 
a malfunction.
Do not install in any place at a temperature of more than 40°C or less 
than 0°C or exposed to direct sunlight.
Doing so may cause deformation or malfunction.
Do not apply AC100V or AC200V to the remote controller. The maximum 
voltage that can be applied to the remote controller is 15V.
The remote controller may be damaged or may generate heat and cause a 
fire.
Do not install in any steamy place such a bathroom or kitchen.
Avoid any place where moisture is condensed into dew. Doing so may cause 
an electric shock or a malfunction.
Do not install in any place where acidic or alkaline solution or special 
spray are often used.
Doing so may cause an electric shock or malfunction.
Use standard wires in compliance with the current capacity.
A failure to this may result in an electric leakage, heating or fire.
Do not touch any control button with your wet hands.
Doing so may cause an electric shock or a malfunction.
Do not wash with water.
Doing so may cause an electric shock or a malfunction.
Do not press any control button using a sharp object.
Doing so may cause an electric shock or a malfunction.
Put on gloves during installation.
It could cause injury.
 2  Confirming the Supplied Parts
 1 Safety 
Precautions
 3  How To Install
 4  Test  Run
 5 Function 
Selection
 5  Function  Selection
Remote controller body 
Remote controller cover
Switch box two units
15 or less
Wall
Bushing
Wiring pipe
Lock nut
Switch box
Seal around here 
with putty.
Remote control 
cord
For taking cord out of top of 
remote controller
Seal around here 
with putty.
For taking 
cord out from 
back of remote 
controller
Remote control cord
Use surface 
raceways
Switch box for two units
Seal the remote 
control cord lead-in 
hole with putty.
(See 2 above)
Remote control cord
 (See 5 below)
Cross recessed pan 
head screw
Wood screw
Remote control cord
 (See 5 below)
F
   Button
K
 “Extra Low” fan 
speed button 
OPERATION button 
 Ahead
L
   ON/OFF button
E
 Fan speed 
Adjustment button
M
 CLEAR button
J
 OPERATION buttons 
 Back
D
 Function selector button
C
   ON/OFF (DAY) button
G
   CLOCK buttons   Back   Ahead
B
   MENU (MONITOR/SET) button
A
 BACK button
A
C
Select from 
item1.
 Hold down the A button 
and press the C button 
for 2 seconds.
 Hold down the A button and press 
the C button for 2 seconds.
        
[2] A C
[3] B
[4] B
[5] C
        
[6] A C
or L
A
[1] Stop the Lossnay to start remote controller function selection mode. 
[2] Select from item1. 
[3] Select from item2. 
[4] Make the setting. (Details are specified in item3) 
[5] Setting completed. 
[6] Change the display to the normal one. (End)
(Hold down the A button and 
press the C button for 2 seconds.)
Item 1
Press the 
B button.
Normal display (Display when 
the Lossnay unit is not running)
Press the 
B button.
Press the 
A button.
Press the 
B button.
*
3
Function limit 
(“FUNCTION 
SELECTION”)
Change Language 
(“CHANGE LANGUAGE”)
Operation function limit setting (“LOCKING FUNCTION”)
Press the B button.
*
1
*
2
*
3
 24-hour ventilation setting (“24HR VENTILATION”)
See [1] (1)
See [2] (1)
See [2] (2)
Item 3
(Setting content)
Item 2
Remote Controller Function Selection Mode
See [3] (1)
See [3] (2)
See [3] (3)
Use of clock setting (“CLOCK”)
Press the B button.
Timer function setting (“WEEKLY TIMER”)
Contact number setting for error situation (“CALL.”)
See [4] (1)
See [4] (2)
Display change 
(“DISP MODE 
SETTING”)
See [5] (1)
See [5] (2)
See [5] (3)
See [5] (4)
See [5] (5)
See [5] (6)
See [5] (7)
See [5] (8)
See [5] (9)
See [6] (1)
See [6] (2)
See [6] (3)
See [6] (4)
Interlock mode setting (“INTERLOCK MODE”)
Press the B button.
Pulse input setting (“INPUT SIGNAL”)
Delayed operation settings (“DELAY OPERATION”)
Exhaust operation settings for air conditioner defrosting (“EA SETTING DEFROST”)
(Hold down the A button 
and press the C button for 
2 seconds, or L button)
NOTE
To return to the normal display, 
hold down the A button and 
press the C button for 2 seconds.
Dot display
The language that is selected 
in CHANGE LANGUAGE 
mode appears on this display. 
English is set in this manual.
Mode selection 
(“MODE 
SELECTION”)
Press the 
A button.
Press the 
B button.
Installation settings 
(“LOSSNAY 
FUNCTION”)
Press the 
B button.
Press the 
A button.
Supply fan speed setting (“SA SETTING”)*
1
Press the B button.
Exhaust fan speed setting (“EA SETTING”)*
1
Power supply / exhaust when operation starts (“POWER VENT START”)
Subordinate Lossnay settings (“
SUB
 SET”)
Power supply ON/OFF/AUTO (“RECOVERY SETTING”)
Operation monitor output selection (“OPERATION MONITOR”)
Exhaust fan speed selection for cold region intermittent operation (“EA SETTING INTERMIT”)
Night purge setting (“NIGHT PURGE”)*
2
Bypass automatic ventilation priority setting (“BYPASS SETTING”)
Press the 
B button.
Interlocking settings 
(“INTERLOCK 
SETTING”)
Press the 
A button.
Press the 
A button.
Change Language 
(“CHANGE LANGUAGE”)
*
3
Press the 
A button.
Filter cleaning  setting (“MAINTENANCE SIGN”)
Press the B button.
Lossnay cores cleaning setting (“MAINTENANCE SIGN”)
46
10
10
20
7
30
30
102
44
φ6
φ 6
102
20
25
25
20
83,5±0,4
73
External size 
of remote 
controller
Extra space 
around remote 
controller
To Lossnay unit A controller 
terminal block
There is no polarity.