Mitsubishi Electronics FX3U-CF-ADP Manual Do Utilizador
10 Troubleshooting
10.1 Troubleshooting procedure
103
FX
3U
-CF-ADP User's Manual
1
Introduc
tion
2
S
pecifi
cation
3
Sy
stem
stem
Configurati
o
n
4
Ins
tal
tal
lation
5
Wi
rin
rin
g
6
Functi
o
n
s
7
Bef
o
o
re
Programm
ing
8
C
F
-AD
P
Appl
ied
Ins
tructi
tructi
ons
Explanati
o
n
9
Program
Examples
10
T
roubl
esho
oti
n
g
37
Outside device point number range in mixed type
specification
specification
The number of written points/read points specified by the parameter is
outside the setting range.
Something may be wrong with mixed type instructions.
Check the parameter contents, execution order, etc. in mixed type
instructions.
outside the setting range.
Something may be wrong with mixed type instructions.
Check the parameter contents, execution order, etc. in mixed type
instructions.
38
Mixed type instruction execution error
The number of written/read points specified by the parameter is outside
the setting range.
Check the parameter contents, execution order, etc. in mixed type
instructions.
the setting range.
Check the parameter contents, execution order, etc. in mixed type
instructions.
42
Response device type error
43
Frame number error
46
Too many characters
The character string exceeds 512 full-width characters, or the data
name exceeds 32 full-width characters.
name exceeds 32 full-width characters.
200
System error
Something may be wrong with the hardware.
Contact your local Mitsubishi Electric distributor.
Contact your local Mitsubishi Electric distributor.
201
Power shutdown history reading error
Check whether a CompactFlash
TM
card having sufficient free space is
mounted correctly. When a CompactFlash
TM
card is mounted correctly,
something may be wrong with the hardware.
Contact your local Mitsubishi Electric distributor.
Contact your local Mitsubishi Electric distributor.
202
Power shutdown history writing error
203
Power shutdown history corruption
204
Power shutdown history backup error
205
System error
Something may be wrong with the hardware.
Contact your local Mitsubishi Electric distributor.
Contact your local Mitsubishi Electric distributor.
206
Power shutdown detection
Shutdown of the supply voltage is detected.
Check whether the power is supplied correctly.
Check whether the power is supplied correctly.
300
SDRAM error
Something may be wrong with the hardware.
Contact your local Mitsubishi Electric distributor.
Contact your local Mitsubishi Electric distributor.
301
ROM error
302
EPROM error
303
SRAM error
304
SUM check error
400
CompactFlash
TM
card unmounted error
The CompactFlash
TM
card is not mounted in the CompactFlash
TM
card
slot.
Mount the CompactFlash
TM
card correctly in the CompactFlash
TM
card
slot.
401
CompactFlash
TM
card error
The CompactFlash
TM
card may be defective.
Replace the CompactFlash
TM
card with another one.
402
CompactFlash
TM
card mount error
The CompactFlash
TM
card is not formatted correctly.
Format the CompactFlash
TM
card, or replace it with another one.
404
CF free space acquisition error
The CompactFlash
TM
card may be defective.
Format the CompactFlash
TM
card, or replace it with another one.
405
CF FULL
The CompactFlash
TM
card is full.
Delete unnecessary data, or replace the CompactFlash
TM
card with
another one.
406
Directory creation error
A folder was not able to be created in the CompactFlash
TM
card.
Check whether the number of files and folders in the root directory in
the CompactFlash
TM
card does not exceed 512.
Check whether the CompactFlash
TM
card is formatted, and whether it
is ready for data writing.
407
CompactFlash
TM
card format error
The CompactFlash
TM
card is not formatted correctly.
Check whether the CompactFlash
TM
card is mounted correctly.
Format the CompactFlash
TM
card, or replace it with another one.
500
Line file error
Access to the file management information file has failed.
Check whether the CompactFlash
TM
card is mounted correctly.
501
ID table open error
The file management information was not able to be read from the
CompactFlash
TM
card.
When reading or deleting a file, confirm that the target file exists.
502
ID table write error
The file management information was not able to be created in the
CompactFlash
TM
card.
Check whether the CompactFlash
TM
card is ready for data writing.
Error
code
Error definition
Error corrective action