Mitsubishi Electronics FX3U-CF-ADP Manual Do Utilizador

Página de 124
5 Wiring
5.4 Power OFF procedure
31
FX
3U
-CF-ADP User's Manual
1
Introduc
tion
2
S
pecifi
cation
3
Sy
stem
 
Configurati
o
n
4
Ins
tal
lation
5
Wi
rin
g
6
Functi
o
n
s
7
Bef
o
re
 
Programm
ing
8
C
F
-AD
P
 Appl
ied 
Ins
tructi
ons
 
Explanati
o
n
9
Program 
Examples
10
T
roubl
esho
oti
n
g
5.4
Power OFF procedure
Make sure to perform either of the following procedures when turning OFF the power of the CF-ADP.
• Power OFF procedure using the CF card ACCESS switch
→ Refer to Subsection 5.4.1
• Power OFF procedure using the applied instruction for the CF-ADP
→ Refer to Subsection 5.4.2
5.4.1
Power OFF procedure using the CF card ACCESS switch
1
Set the main unit to the STOP mode, or set the 
applied instruction for the CF-ADP to the unactuated 
status.
2
Turn OFF the CF card ACCESS switch, and then 
confirm that the ACCESS LED (A in the figure on the 
right) and BUFFER LED (B in the figure on the right) 
are completely OFF.
3
Turn the power of the CF-ADP OFF.
5.4.2
Power OFF procedure using the applied instruction for the CF-ADP
1
Execute the FLCMD instruction to 
unmount the CompactFlash
TM
 card.
2
Confirm that the FLCMD instruction 
is completed normally.
3
Turn the power of the CF-ADP OFF.
5.4.3
Caution on power OFF
If the power is turned OFF while the CompactFlash
TM
 card is being accessed (ACCESS LED is lit or
flickering), the buffered data is erased. Also files or CompactFlash
TM
 card itself may be damaged.
Do not turn the power OFF while the ACCESS LED is lit or flickering.
(A)
(B)
M0
RST
M8329
1.Execute the FLCMD instruction,
K1
H200
   FNC304
    FLCMD
M0
Y0
SET
M0
SET
X000
Y1
SET
M8029
M0
RST
If the FLCMD instruction is abnormally completed,
do not turn the power of the CF-ADP OFF .
2.Confirm that the FLCMD instruction is normally completed.
3.Turn the power of the CF-ADP OFF.
Execution
completion
Abnormal
end