Toshiba 4200FA Folheto

Página de 2
TOSHIBA
 4200FA XT UPS 
Installation Planning Guide for 15-80kVA UPS 
Standard System: 208v Input, 208/120V Output 
Rev. 1.03 
Page 2 of 2 
4200FA-IPG-208v-XT1 
 
Important Notes: 
 
 
1. Maximum Current required at Primary AC Input based on full load output and maximum 
battery charging current. 
2. Output load conductors are to be installed in separate conduit from input conductors. 
3. Control wires and power wires are to be installed in separate conduits. 
4. Recommended AC input and output overcurrent protection based on continuous full load 
current per NEC. 
5. Wiring shall comply with all applicable national and local electrical codes. 
6. Grounding conductors to be sized per NEC Article 250-122.  Neutral conductors to be sized 
per NEC Article 310.15. 
- Primary AC Input: 3
φ, 4-wire + ground. 
- AC Output: 3
φ, 4-wire + ground. 
- DC Input: 2-wire (Positive/Negative) + ground. 
7. 
Nominal battery voltage based on the use of VRLA type batteries 
(2.0 volts / cell nominal). 
8. Maximum battery discharge current based on lowest permissible discharge voltage of 1.6 
VPC. 
9. DC wires should be sized to allow not more than a 2-volt drop at maximum discharge 
current. 
10. Weights include internal batteries. 
11. Sizing calculations based on the following assumptions: 
-  Not more than 3 current-carrying conductors installed in steel conduit in ambient temperature of 30 
degrees C. 
-  Temperature rating of conductors and terminals: 90 deg. C. 
-  Feeder distance calculations based on NEC Tables 8 and 9 data, allowing for 2% AC voltage drop. 
-  Reference: 2002 NEC Handbook. Consult latest edition of applicable national and local codes for 
possible variations. 
12. Ratings of wires and overcurrent devices are suggested minimums.  Consult with a  
      registered Professional Engineer within your local area for proper size selections. 
 
 
 
 
TOSHIBA
 INTERNATIONAL CORPORATION 
13131 West Little York Road 
Houston, TX 77041 
Telephone: 800.231.1412; 713.466.0277 
Fax: 713.896.5212 
Corporate Web Site: 
www.tic.toshiba.com
 
Group Web Site:  
www.toshibaups.com