Enviro 170S5FG Manual Do Utilizador

Página de 30
MQL • E
LECTRIC
H
EAT
8
Notes:  
1. Blow thru heaters can have a maximum of two stages.
2. VFD controllers cannot be supplied with blow thru heaters.
3. Specific kW ratings are available within the ranges shown.  Refer to selection program.
4. Heaters above 480v must utilize one time secondary limits only.
Notes:  
1. Draw thru heaters can have a maximum of four stages.
2. All heaters that have an AMP draw greater than 48 AMPs will have a minimum of two stages.
3. Specific kW ratings are available within the ranges shown.  Refer to selection program.
4. Heaters above 480v must utilize one time secondary limits only.
Min Max
Min Max
Min Max
Min Max
Min Max
Min Max
Min
Max
Min
Max
Min
Max
kW
3
5
3
5
4
5
AMPs 26.1 43.5 26.1 43.5 34.8 43.5
kW
3
10
3
10
4
10
6.0
16
7
16
9
20
AMPs 14.4 48.1 14.4 48.1 19.2 48.1 28.8 76.9 33.7 76.9 43.3 96.2
kW
3
11
3
11
4
11
6.0
18
7
18
9
22
AMPs 13.0 47.8 13.0 47.8 17.4 47.8 26.1 78.3 30.4 78.3 39.1 95.7
kW
3
13
3
13
4
13
6.0
22
7
22
9
26
AMPs 10.8 46.9 10.8 46.9 14.4 46.9 21.7 79.4 25.3 79.4 32.5 93.9
kW
3
13
3
20
4
26
4.0
26
7
28
9
34
12
46
14
46
16
46
AMPs 8.3 36.1 8.3 55.5 11.1 72.2 11.1 72.2 19.4 77.7 25.0 94.4 33.3 127.7 38.9 127.7 44.4 127.7
kW
3
13
3
20
4
26
4.0
26
7
32
9
34
12
49
14
49
16
49
AMPs 7.5 32.6 7.5 50.2 10.0 65.3 10.0 65.3 17.6 80.3 22.6 85.3 30.1 123.0 35.1 123.0 40.2 123.0
kW
3
13
3
20
4
26
4.0
26
7
52
9
64
12
76
14
88
16
96
AMPs 3.8 16.3 3.8 25.1 5.0 32.6 5.0 32.6 8.8 65.3 11.3 80.3 15.1 95.4 17.6 110.4 20.1 120.5
kW
3
13
3
20
4
26
4.0
26
7
52
9
64
12
76
14
88
16
96
AMPs 3.0 13.1 3.0 20.1 4.0 26.1 4.0 26.1 7.0 52.2 9.0 64.3 12.0 76.3 14.1 88.4 16.1 96.4
UNIT 
VOLTAGE 
AND PHASE
DRAW-THRU ELECTRIC HEAT
Unit Size
02
03
04
06
08
10
12
14
17
Single Phase
115
230
208
277
Three Phase
208
230
460
575
Min Max
Min Max
Min Max
Min Max
Min Max
Min Max
Min
Max
Min
Max
Min
Max
kW
3
5
3
5
4
5
AMPs 26.1 43.5 26.1 43.5 34.8 43.5
kW
3
9
3
9
4
9
6
9
7
9
AMPs 14.4 43.3 14.4 43.3 19.2 43.3 28.8 43.3 33.7 43.3
kW
3
11
3
11
4
11
6.0
11
7
11
9
11
AMPs 13.0 47.8 13.0 47.8 17.4 47.8 26.1 47.8 30.4 47.8 39.1 47.8
kW
3
13
3
13
4
13
6.0
13
7
13
9
13
AMPs 10.8 46.9 10.8 46.9 14.4 46.9 21.7 46.9 25.3 46.9 32.5 46.9
kW
3
13
3
16
4
16
4.0
16
7
16
9
16
12
16
14
16
AMPs 8.3 36.1 8.3 44.4 11.1 44.4 11.1 44.4 19.4 44.4 25.0 44.4 33.3 44.4 38.9 44.4
kW
3
13
3
18
4
18
4.0
18
7
18
9
18
12
18
14
18
16
18
AMPs 7.5 32.6 7.5 45.2 10.0 45.2 10.0 45.2 17.6 45.2 22.6 45.2 30.1 45.2 35.1 45.2 40.2 45.2
kW
3
13
3
20
4
26
4.0
26
7
38
9
38
12
38
14
38
16
38
AMPs 3.8 16.3 3.8 25.1 5.0 32.6 5.0 32.6 8.8 47.7 11.3 47.7 15.1 47.7 17.6 47.7 20.1 47.7
kW
3
13
3
20
4
26
4.0
26
7
46
9
46
12
46
14
46
16
46
AMPs 3.0 13.1 3.0 20.1 4.0 26.1 4.0 26.1 7.0 46.2 9.0 46.2 12.0 46.2 14.1 46.2 16.1 46.2
06
08
UNIT 
VOLTAGE 
AND PHASE
Three Phase
208
230
460
575
BLOW-THRU ELECTRIC HEAT
Unit Size
14
17
10
12
04
Single Phase
02
03
208
230
277
115
ENVIRO-TEC