INSTALLATION CHECKLIST
Water Heater Location 
Requirements
…  Centrally located with the water piping system. Located 
as close to the gas piping and vent pipe system as pos-
sible.
…  Located indoors and in a vertical position. Protected   
from freezing temperatures.
…  Proper clearances from combustible surfaces main-
tained and not installed directly on a carpeted floor. 
Sufficient room to service the water heater.
…  Provisions made to protect the area from water dam-
age. Properly sized drain pan installed and piped to an 
adequate drain.
…  Installation area free of corrosive elements and      
flammable materials.
Condensate Line
…
  Drain stem is fully inserted in the elbow and glued   
properly.
…
  Trap aligned so that the exhaust pipe is in a vertical 
position close to the surface of the water heater.
…
  Line properly sloped to adequate drain or approved    
condensate pump.
…
  Properly vented.
…
  Protected from freezing (if required).
Vent Pipe System
…
 
Vent pipe and fittings of approved material. 
…
 
Acceptable size, length, and number of elbows on air 
inlet pipe.
…
 
Acceptable size, length, and number of elbows on 
exhaust outlet pipe.
…
  Add the air inlet filter per the manufacturer’s instruction.
…
 
Installed in accordance with prevailing provisions of 
Local codes, or in the absence of such, National  Fuel  
Gas Code, NFPA 54, ANSI Z223.1-Latest Edition.  Ca-
nadian Installations must be performed in accordance 
with CAN/CGA-B149.
…
 
All 2” horizontal piping sloped down toward the water 
heater at 1/4” per foot. 3” piping 
sloped down towards 
the heater
 at 1/8” per foot. 
…
  Not obstructed in any way.
Vent Termination
    
       
Horizontal
…  Correct relationship - outlet to inlet.
…  12” Min. above grade/snow level.
…  2” exhaust outlet/air inlet pipe sloped down towards 
water heater at 1/4” per foot.  3” piping 
sloped down 
towards the heater
 at 1/8” per foot. 
…  Away from corners, other vents, windows, etc.
 Alternate 
Horizontal
…
 
Correct relationship - outlet to inlet.
…
 
12” Min. above anticipated snow level.
…
  2” exhaust outlet/air inlet pipe sloped down towards 
water heater at 1/4” per foot.  3” piping sloped down 
towards the heater at 1/8” per foot. 
…  Away from corners, other vents, windows, etc.
       
Vertical
…  Inlet - 12” Min. above roof/snow level.
…  Correct relationship - outlet to inlet.
…  Away from corners, other vents, windows, etc.
 
Concentric
…  12” Min. above grade/snow level.
…  2” exhaust outlet/air inlet pipe sloped down towards 
water heater at 1/4” per foot.  3” piping 
sloped down 
towards the heater 
at 1/8” per foot. 
…  Away from corners, other vents, windows, etc.
Water System Piping
…  Temperature and pressure relief valve properly 
installed with a discharge line run to an open drain and 
protected from freezing.
…  All piping properly installed and free of leaks.
…  Heater completely filled with water.
…  A properly sized expansion tank must be installed on all 
closed systems.
…  A tempering valve (provided) must be installed per the 
manufacturer’s instructions.
Gas Supply and Piping
…  If using a flexible gas connector, make sure its rating 
tag matches or exceeds the input of the  water heater.
…  Adequate pipe size and of approved material.
…  Gas supply is the same type as listed on the water    
heater data plate.
…  Gas line equipped with full opening shut-off valve,   
union and drip leg.
…  Approved pipe joint compound used.
…  Chloride-free soap and water solution or other  ap-
proved means used to check all connections and fit-
tings for possible gas leaks.
Electrical Connections
…  Unit connected to a dedicated power supply.
…  Unit connected to a 120V electrical supply.
…  Proper polarity.
…  Water heater properly grounded.
…  Installed in accordance with prevailing provisions of 
local codes, or in the absence of such, National Fuel  
Gas Code, NFPA 54, ANSI Z223.1-Latest Edition.  
Canadian installations must be performed in accor-
dance with CAN/CGA-B149.