Honeywell MS-9600LSC Manual Do Utilizador

Página de 208
106
MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
Programming
Master Programming Level
A flashing cursor is positioned in the lower left corner of the display.  Enter a delay time consisting 
of three digits, such as 009 for nine seconds.  Upon entering the third digit, the time delay will be 
stored in the control panel memory and the display will return to the Delay Screen which will indi-
cate the new delay time.
Note that the FACP can be programmed for either PAS or Pre-signal operation, not both.  Refer to 
“Edit Detector” on page 69 for programming details.
Waterflow Delay
A delay can be added prior to declaring a waterflow type of alarm.  Be careful to include any built-
in delays of the waterflow device.  The factory default setting for Waterflow delay is 000 for no 
delay.  To select a Waterflow delay of 01 to 90 seconds for all devices programmed for Waterflow 
delay, press 3 while viewing Timer Screen #1.  The following screen will be displayed:
A flashing cursor is positioned in the lower left corner of the display.  Enter a delay time consisting 
of two digits, such as 25 for twenty-five seconds.  Upon entering the second digit, the time delay 
will be stored in the control panel memory and the display will return to the Delay Screen which 
will indicate the new delay time.
AC Loss Delay
The reporting of a loss of AC power to a central station can be delayed by programming the length 
of the desired delay.  The factory default setting is 2 hours.  Press 1 while viewing Timer Screen #2 
to display the following: 
Pressing 1 while viewing AC Loss Delay Screen #1 will program the FACP to transmit an AC Loss 
report immediately to the central station.
   TIMER
1=PAS DELAY   000
2=PRE SIGNAL  000
3=WATERFLOW   000
Timer Screen #1
  WATERFLOW DELAY
RANGE 0-90 SECONDS
Waterflow Delay Screen
   TIMER
1=AC LOSS DELAY
Timer Screen #2
 AC LOSS DELAY
1=NO DELAY
2=ENTER DELAY
AC Loss Delay Screen #1