Programming
Master Programming Level
Auto Silence
The Auto Silence feature, when enabled, automatically silences all main circuit board silenceable 
notification appliances after a programmed length of time.  To enable this feature and program the 
time delay before Auto Silence activation, press 1 while viewing NAC Screen #2.  The following 
screens will be displayed:
To disable the Auto Silence feature, press 1 for No while viewing Auto Silence Screen #1.  To 
enable the Auto Silence feature, press the number corresponding to the time delay which will 
elapse before Auto Silence activates.  When a time delay is selected, the information will be stored 
in memory and the display will return to NAC Screen #2.
Coding
The Coding feature allows the programmer to select the type of output that the main circuit board 
notification appliances will generate when activated.  Pressing 2 while viewing NAC Screen #2 
will cause the following displays to appear:
   NAC #
1=AUTO SILENCE
2=CODING
          TEMPORAL
NAC Screen #2
  AUTO SILENCE
1=NO
2=5 MINUTES
3=10 MINUTES
Auto Silence Screen  #1
  AUTO SILENCE
1=30 MINUTES
Auto Silence Screen #2
  AUTO SILENCE
1=15 MINUTES
2=20 MINUTES
3=25 MINUTES
Auto Silence Screen #3
     CODING
1=STEADY
2=MARCH TIME
3=CALIFORNIA
Coding Screen  #1
     CODING
1=TEMPORAL
2=TWO STAGE 3 MIN
3=TWO STAGE 5 MIN
Coding Screen #2