MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
131
Master Programming Level
Programming
ANN-RLY Options
Pressing 2 for Module Options while viewing ANN-BUS Address Screen when the ANN-RLY 
option is selected will cause the following screen to be displayed:
The ANN-RLY module provides ten Form-C relays which can be programmed for various func-
tions.  The initial screen displays Relays 1 through 3.  Pressing the down arrow key will display the 
remaining relays for this module.
To program any of the ANN-RLY relays, while viewing the appropriate ANN-RLY Option screen, 
press the number key corresponding to the relay to be programmed.  Following is a list of the avail-
able programming options for each relay:
Alarm
Supervisory
Supervisory AR
Trouble
Comm Fail
Process Mon
Process Mon AR
AC  Loss
Hazard
Medical
Silenceable Alarm
Zone Active XX
Auto-Configure
The ANN-BUS Auto-Configure features allows the programmer to quickly bring all installed 
ANN-BUS modules online.  The software will search for all ANN-BUS modules and automatically 
program the device type and address into the system.  The ANN-BUS must be enabled for the Auto-
Configure feature to work. 
  
Pressing 3 while viewing ANN-BUS Screen #1 will begin the Auto-Configure process and cause 
the following screen to be displayed: 
  ANN-RLY - ADDR. #
1=RELAY 1      ZONE 00
2=RELAY 2      ZONE 01
3=RELAY 3      ZONE 02
ANN-RLY Options Screen
  ANN-BUS
1=ANN ENABLED
2=OPTIONS INSTALLED
3=AUTO-CONFIGURE
ANN-BUS Screen #1
ANN-BUS
AUTO-CONGFIGURE
IN PROGRESS
PLEASE WAIT
Auto-Configure Screen