Appendix E: Wire Requirements
T-tapping of the SLC loop wiring is allowed for 2-wire (Style 4) configurations.  The total 
resistance of any branch cannot exceed 40 ohms.  The total wire length of all branches cannot 
exceed 10,000 feet (3,000 m).
Connecting external system accessories to the FACP main circuits must be carefully considered to 
ensure proper operation.  It is important to use the correct type of wire, wire gauge and wire run 
length for each FACP circuit.  Reference the chart below to specify wire requirements and 
limitations for each FACP circuit.
Note: 
1. If the SLC loop is to be run in conduit with Notification Appliance Circuits, the risk of 
encountering problems can be greatly reduced by exclusively employing electronic sounders 
instead of more electronically noisy notification appliances such as electromechanical bells or 
horns.
2. If two SLC loops are to be installed in conduit, each loop must be installed in separate conduit.
3. The SLC can be programmed to operate in LiteSpeed mode (factory default setting) for a 
quicker device response time.  While shielded wire is not required in LiteSpeed mode, it is 
recommended that all SLC wiring be twisted-pair to minimize the effects of electrical 
interference.  Use the following table to determine the specific wiring requirements for the 
SLC when unshielded wire is used:   
CIRCUIT CONNECTIONS
WIRE REQUIREMENTS
Circuit Type
Circuit Function
Wire Type and Limitations
Recommended Max. 
Distance
Feet (meters)
Wire Gauge and Compatible Brands
SLC loop
(power-limited)
Connects to 
Addressable Devices
CLIP MODE
Twisted, shielded pair
40 ohms maximum per length 
of Style 6 and 7 loops.  40 ohms 
per branch maximum for Style 4 
loops
10,000 (3,000 m)
8,000 (2,400 m)
4,875 (1,450 m)
3,225 (980 m)
12 AWG (3.25 mm
2
): Genesis 4410, 
     Signal 98230, Belden 9583, WPW999
14 AWG (2.00 mm
2
):Genesis 4408 & 4608 
      Signal 98430, Belden 9581, WPW995
16 AWG (1.30 mm
2
): Genesis 4406 & 4606
      Signal 98630, Belden 9575, WPW991
      Direct Burial Cable Isotec NP713110VNQ-S
18 AWG (0.75 mm
2
): Genesis 4402 & 4602
      Signal 98300, Belden 9574, WPW975
      Direct Burial Cable Isotec NP714110VNQ-S
LITESPEED MODE
Twisted, unshielded pair
40 ohms maximum per length 
of Style 6 and 7 loops.  40 ohms 
per branch maximum for Style 4 
loops
10,000 (3,000 m)
8,000 (2,400 m)
4,875 (1,450 m)
3,225 (980 m)
12 AWG (3.25 mm
2
): Belden 5020UL &
     6020UL, Genesis WG-4315 & WG-4515
14 AWG (2.00 mm
2
):Belden 5120UL &
     6120UL, Genesis WG-4313 & WG-4513
16 AWG (1.30 mm
2
): Belden 5220UL &
     6220UL, Genesis WG-4311 & WG-4511
18 AWG (0.75 mm
2
): Belden 5320UL &
     6320UL, Genesis WG-4306 & WG-4506
Untwisted, unshielded pair
1
3,000 (900 m)
12-18 AWG (3.25 - 0.75 mm
2
) using listed wire
 ACS-BUS
(EIA-485)
(power-limited)
Connects to 
annunciator modules
Twisted pair with characteristic 
impedance of 120 ohms
6,000 (1,800 m)
12 AWG (3.25 mm
2
)
ANN-BUS
(EIA-485)
(Power-limited)
Connects to 
annunciator modules
Twisted pair
6,000 (1,800 m)
Refer to “ANN-BUS Wiring” on page 23 for wire 
requirements.
EIA-232
(power-limited)
connects to remote 
PC computer
Twisted, shielded pair
50 (15 m)
18 AWG (0.75 mm
2
) minimum
MMF-300 and 
MMF-301
(power-limited)
Initiating Device 
Circuit
Maximum loop wire resistance 
is 40 ohms for the MMF-300 
and 20 ohms for the MMF-301
2,500 (760 m)
12-18 AWG (3.25 - 0.75 mm
2
)
MMF-302
(power-limited)
Initiating Device 
Circuit
No more than a 2.4 volt drop 
allowed at end of circuit.  
Maximum loop wire resistance 
is 25 ohms
2,500 (760 m)
12-18 AWG (3.25 - 0.75 mm
2
)
CMF-300
(power-limited)
Notification Appliance 
Circuit
In alarm, no more than a 1.2 
volt drop allowed at end of 
circuit
Distance limitation set 
by 1.2 volt maximum 
line drop
12-18 AWG (3.25 - 0.75 mm
2
)
Table E.1  FACP Wire Specifications
1
When using untwisted, unshielded wire, full conduit is recommended for optimum EMI/RFI protection.