MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
105
Master Programming Level
Programming
Timers
Timer delays for PAS, Pre-signal and waterflow activation can be programmed by pressing 1 while 
viewing System Setup Screen #2.  The following screen will be displayed: 
PAS (Positive Alarm Sequence) Delay
The factory default setting for PAS is 000 for no delay.  To select a PAS delay of 001 to 180 seconds 
for all devices programmed for PAS, press 1 while  viewing Timer Screen #1.  The following dis-
play will appear: 
A flashing cursor is positioned in the lower left corner of the display.  Enter a delay time consisting 
of three digits, such as 005 for five seconds.  Upon entering the third digit, the time delay will be 
stored in the control panel memory and the display will return to the Delay Screen which will indi-
cate the new delay time.
Pre-signal Delay
The factory default setting for Pre-signal delay is 000 for no delay.  To select a Pre-signal delay of 
001 to 180 seconds for all devices programmed for Pre-signal, press 2 while viewing Timer Screen 
#1.  The following screen will be displayed:
   SYSTEM SETUP
1=TIMERS
2=NAC
3=RELAYS
System Setup Screen #2
      TIMERS
1=PAS DELAY      000
2=PRE SIGNAL     000
3=WATERFLOW      000
Timer Screen #1
      TIMERS
1=AC LOSS DELAY  000
Timer Screen #2
   TIMERS
1=PAS DELAY   000
2=PRE SIGNAL  000
3=WATERFLOW   000
Timer Screen #1
     PAS DELAY
RANGE 0-180 SECONDS
PAS Delay Screen
  PRESIGNAL DELAY
RANGE 0-180 SECONDS
Pre-signal Delay Screen