Honeywell MS-9600UDLSE Manual Do Utilizador

Página de 208
158
MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
Operating Instructions
Presignal
4.18  Presignal
Presignal option programs an initiating device to delay the activation of NACs and/or control mod-
ules while allowing visual verification by a person.  Once a detector or monitor module triggers an 
alarm, the onboard piezo sounds immediately, but the NACs are not activated for a user pro-
grammed time duration of up to three minutes. Note that the alarm relay and communicator will 
respond to the initial alarm immediately.  In addition, Zone 98 will activate.  This zone can be pro-
grammed to a control module which may be used to activate a sounder or indicator which the 
installer designates as a Presignal indication.  Do not assign Zone 98 to a Notification Appliance 
Circuit when using this zone to indicate a Pre-signal condition.
After the programmed delay, the NACs will activate if the source of the alarm is not cleared.  Note 
that if a second alarm occurs during the programmed time delay, the alarm will be processed imme-
diately, causing activation of the appropriate output zones.  The events which occur upon Presignal 
activation are as follows: 
• onboard piezo sounds immediately
• control panel LCD display will indicate a presignal event and the active point
• control points programmed to Zone 98 will activate
• annunciators (if enabled) will sound the local piezo, and pulse the alarm LED and zone LED
• outputs (NACs and control modules) of associated zones will be inhibited from activating 
for a user programmed time delay of up to three minutes
• second alarm occurring anytime during the time delay will cause immediate activation of all 
associated outputs
Presignal does not affect monitor modules programmed as waterflow, supervisory, process moni-
toring or remote switches.  Presignal operation requires the approval of the local Authority Having 
Jurisdiction.
4.19  Positive Alarm Sequence
PAS (Positive Alarm Sequence) option will program a smoke detector to delay panel activation 
(including alarm relay and communicator) for a period of 15 seconds.  Zone 97, however, will acti-
vate immediately and may be used to connect a signaling device to indicate PAS activation.  Do not 
assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate a PAS condi-
tion.
When a detector triggers an alarm, the onboard piezo sounds immediately, but the NACs are pre-
vented from activating for 15 seconds.  This inhibit time is factory set and cannot be changed.  
Pressing the Alarm Silence or Acknowledge/Step key during the 15 second inhibit time will silence 
the piezo sounder and start a timer which prevents activation of NACs for an additional time dura-
tion which can be user programmed for up to three minutes.  After the programmed delay, the 
NACs will activate if the source of the alarm is not cleared.  Note that if a second alarm occurs dur-
ing either time delay, the alarm will be processed immediately, causing activation of the appropriate 
output zones.  The events which occur upon PAS activation are as follows:
• onboard piezo sounds immediately
• control panel LCD display will indicate a presignal event and the active point
• control points programmed to Zone 97 will activate
• ACS annunciators (if enabled) will pulse the Zone 97 PAS LED immediately upon PAS 
activation.  They will sound the local piezo, and pulse the alarm, associated zone and 
detector address point LEDs after 15 seconds of an unacknowledged PAS activation.  Note 
that if the Alarm Silence or Acknowledge/Step button is pressed, the annunciators will be 
inhibited from activating for an additional time delay
• outputs (NACs and control modules) of associated zones will be inhibited from activating 
for a factory set duration of 15 seconds