Honeywell MS-9600UDLSE Manual Do Utilizador

Página de 208
178
MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
Appendix A: Software Zones
A.1  Correlations
Setup and configuration of an addressable system is different than a conventional system.  In a 
conventional system, assignment of input devices (smoke detectors, pull stations, heat detectors, 
etc.) to zones is accomplished through wiring.  The wiring is direct from clearly marked panel 
terminals to any device assigned to a particular zone.  Connection of output devices (horns, bells, 
strobes, etc.) in a conventional system is accomplished by direct wiring of the output devices to 
Notification Appliance Circuit terminals.
In an addressable system, a minimum of a single pair of wires (SLC communication loop) is used 
to connect all addressable input and output devices.  Communications between the FACP (Fire 
Alarm Control Panel) and all addressable devices takes place over the wire pair which originates 
from the FACP.  Software programming is used to configure the system as opposed to direct wiring.  
Zone assignments are created via software means, hence the term software zones.
Setup of an FACP software zone is accomplished by panel programming.  Each addressable device 
can be assigned to a maximum of five software zones.  Each software zone, however, may have 
from 1 to 99
1
 addressable input devices assigned to it and from 1 to 99
 addressable output devices 
assigned to it.  
Monitor and control modules comprise one group of 99
 addresses, with each module having a 
unique address from 1 to 99
.  Detectors comprise a separate group of 99
 addresses, each detector 
having a unique address from 1 to 99
 in its group.  Be careful not to duplicate addresses within any 
one group (modules and detectors).  Refer to the following page for an example of zoning.  
In the example on the following page:
Zone 01 has the following addressable devices assigned to it:
• SD350 smoke detectors with addresses 01 and 02
• MMF-300 monitor module with address 01
• MMF-302 monitor module with address 02 and 03
• CMF-300 control modules with addresses 050607, 09, and 13
Zone 02 has the following addressable devices assigned to it:
• MMF-302 monitor module with addresses 02 and 03
• CP350 smoke detectors with addresses 03 and 04
• CMF-300 control modules with addresses 0809, and 10
Zone 03 has the following addressable devices assigned to it:
• SD350 smoke detectors with addresses 0506, and 07
• MMF-302 control module with address 04
• CMF-300 control modules with addresses 0911, and 12
The example points out some of the key assignment features of the FACP.  Addresses of detectors 
are not duplicated.  Addresses of monitor and control modules are not duplicated.  The control 
module with address 09 is assigned to three software zones (providing floor above and floor 
below).  Be careful to properly plan the installation prior to installing any devices.
1. CLIP or Classic Loop Interface Protocol devices (modules and detectors) can only have 
unique addresses of 1 to 99.  Newer LiteSpeed devices (modules and detectors) can have 
unique addresses of 1 to 159 which means each zone can have up to 159 input and output 
devices assigned to it.