Honeywell MS-9600UDLSE Manual Do Utilizador

Página de 208
MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
39
Accessories
Product Description
Examples: 
FACP Input programmed to Zone 33 goes into alarm, the programmed message for Zone 33 
[Message 1, 2, 3, 4 or 5] will play over the ACC-25/50ZS Series output circuit 1 which 
corresponds to FACP Zone 33.  
FACP Input programmed to Zone 1 and Zone 34 (Zone 1 is programmed for a Message [1, 2, 
3, 4 or 5] and Zone 34 is programmed for No Message) goes into alarm, the programmed 
message for Zone 1 will play over the ACC-25/50ZS Series output circuit 2 which corresponds 
to FACP Zone 34.
If two or more input zones are active at the same time, the highest priority message will turn on 
(Message 1 is highest priority and Message 5 is lowest) and play over the corresponding audio 
panel output circuit(s).
Zone 32 is an All-Call zone.  All audio panel output circuits will turn on if Zone 32 is activated 
and its programmed message will play (or the highest priority message currently being 
played).
A fault at the ACC-25/50ZS Series panel will cause the FACP to indicate a System Trouble and the 
display will indicate a Voice Evac Fault.
The only connection between the FACP and ACC-25/50ZS Series audio panel is a pair of commu-
nication wires connected between the A(+)/B(-) terminals on TB9 of the FACP and TB1 terminals 
2 & 3 of the ACC-ZPMK module on the audio panel.
A (+)
B (-)
FACP
ACC-ZPMK
on ACC-25/50ZS Series
Figure 1.16  FACP Connection to ACC-25/50ZS Series Audio Panel
ANN-BUS 
acczp
m