Honeywell MS-9600UDLSE Manual Do Utilizador

Página de 208
MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
55
Optional Modules and Devices
Installation
2.6.2  4XTMF Transmitter Module Installation
The 4XTMF provides a supervised output for a local energy municipal box transmitter in addition 
to alarm and trouble reverse polarity.  A jumper option allows the reverse polarity circuit to open 
with a system trouble condition if no alarm condition exists.  A disable switch allows disabling of 
the transmitter output during testing to prevent accidental calling of the monitoring service.
Local Energy Municipal Box Service (NFPA 72 Auxiliary Fire Alarm Systems):
Supervisory Current: 5.0 mA
Trip Current: 350 mA (subtracted from notification appliance power)
Coil Voltage: 3.65 VDC
Maximum Coil Resistance: 14.6 ohms
Maximum allowable wire resistance between panel and trip coil: 3 ohms
Municipal Box wiring can leave the building
Figure 2.14  Wiring Phone Jacks
Green Wire
Red Wire
Green Wire
Red Wire
Tip
Ring
Ring
Tip
Ring
Tip
Tip
Ring
To premises phones
To premises phones
Secondary Lines
Incoming Telco 
Phone Lines
Primary Lines
Incoming Telco Phone 
Lines
Note: Shorting bars inside RJ31X Jack 
removed during male plug insertion
Primary Phone Line PRI
Secondary Phone Line SEC
Male Plug 
Connectors
Female 
Connectors
7 foot cable 
(MCBL-7) 
order separately
DACT-UD2
CAUTION: It is critical that the 
DACT-UD2 be located as the first 
device on the incoming telephone 
circuit to properly function
96
00
ja
cj
.w
mf