Honeywell MS-9600UDLSE Manual Do Utilizador

Página de 208
62
MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
Programming
User Programming
3.2  User Programming
The FACP is completely field programmable and requires no special software skills.  While pro-
gramming the FACP, the fire protection capabilities of the control panel are enabled.  Program-
ming mode will time-out following 10 minutes of inactivity. 
Site-specific programming may be accomplished in three ways:
Autoprogramming Feature - This is a convenient method for quickly bringing the FACP 
addressable SLC devices on-line without the necessity of programming each device 
individually.  Refer to “Autoprogram” on page 66 for a detailed description of 
Autoprogramming
Manual programming or editing, using the FACP keypad or a PC keyboard
Remote Programming and Editing Feature - allows creation and editing of site-specific custom 
programs using a Windows-based computer and modem.  For programs requiring a large 
amount of data entry, this method may be preferred.  A PK-CD programming CD-ROM can be 
ordered for this purpose
Local Programming and Editing Feature - allows creation and editing of site-specific custom 
programs using a Windows-based computer and the DACT-UD2 USB connection on the 
MS-9600UDLS or Serial Port connection on TB7 of the MS-9600LS.  For programs requiring 
a large amount of data entry, this method may be preferred.  A PK-CD programming CD-ROM 
can be ordered for this purpose
The System All Normal screen will be displayed in a programmed system with no active alarms, 
troubles or supervisories, as illustrated below: 
Read Status mode can be entered while the panel is in any mode of operation.  If an alarm or super-
visory event exists at the panel, the event must be cleared before entering Programming mode.  To 
access any of the programming or read status features, the Enter or Mode key must be pressed, 
which will cause the LCD to display the following: 
Pressing 1, while this screen is being displayed, will cause the control panel to enter the Read Sta-
tus feature which allows the user to view the programmed features and status of the control panel  
The Read Status feature is not password protected.  Refer to “Read Status” on page 160 for a 
detailed description of this feature.
Pressing 2 will select user Programming which may only be accomplished by an authorized person.  
After pressing 2, a screen will prompt for a password.  After entering the correct password, the user 
may select from a list of programming options.
Pressing 3 will select Remote Download which allows the user to enable the remote programming 
option.  Refer to the DACT-UD2 manual P/N 53037.
      
     
  SYSTEM ALL NORMAL
  10:00A 010807
1=READ STATUS
2=PROGRAMMING
3=REMOTE DOWNLOAD