MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
67
Master Programming Level
Programming
3.6.2  Point Program
The Point Program option allows the programmer to add a new addressable device to an SLC loop, 
delete an existing device from a loop or change the programming for an existing device.  Pressing 
2, while viewing Programming Screen #1, will select the Point Program option and display the fol-
lowing screen: 
The programmer selects the desired SLC loop by pressing 1 or 2 in Point Program Screen #1, 
which causes the panel to display the following screen: 
Detector Programming
Pressing 1, while viewing Point Program Screen #2, will allow the programmer to add, delete or 
change the programming of an addressable detector.  The following screen will be displayed by the 
control panel: 
Add Detector
Pressing 1 while viewing the Detector Screen will display the following screen which allows the 
programmer to add a new detector address to programming: 
 PROGRAMMING
1=AUTOPROGRAM
2=POINT PROGRAM
3=ZONE SETUP
Programming Screen #1
   POINT PROGRAM
    SELECT LOOP
1=LOOP 1
2=LOOP 2
Point Program Screen #1
   POINT PROGRAM
    SELECT TYPE
1=DETECTOR
2=MODULE
Point Program Screen #2
      DETECTOR
1=ADD
2=DELETE
3=EDIT
Detector Screen
    ADD DETECTOR
ENTER DETECTOR#
***
Add Detector Screen