Honeywell MS-9600UDLSE Manual Do Utilizador

Página de 208
78
MS-9600LS Series Manual — P/N 52646:B2  2/12/2010
Programming
Master Programming Level
3. With the cursor on the last letter of the Noun field, press the zero key again to increment the 
room number to 305.
4. Press the right arrow key to advance the zone field.
5. Select a zone number from 00 to 99.  Z00 (default zone) is the general alarm zone.  Z01 
through Z99 may be selected to link software zones.
Module Programming
Pressing 2, while viewing Point Program Screen #2, will allow the programmer to add, delete or 
change the programming of an addressable module.  The following screen will be displayed by the 
control panel: 
Add Module
Pressing 1 while viewing the Modules Screen will display the following screen which allows the 
programmer to add a new module address to programming: 
A flashing cursor will appear in the position of the first asterisk to the left.  The programmer keys in 
the three digit module address, such as 005.  
When the last digit is keyed-in, the following screen will be displayed: 
POINT PROGRAM
SELECT TYPE
1=DETECTOR
2=MODULE
Point Program Screen #2
      MODULES
1=ADD
2=DELETE
3=EDIT
Modules Screen
     ADD MODULE
ENTER MODULE#
***
Add Module Screen #1
     ADD MODULE
1=CONTROL
2=MONITOR
Add Module Screen #2