Programming
Master Programming Level
Disable
Pressing 2 for Disable, while viewing Zone Setup Screen #1, will display the following screen: 
This screen allows the programmer to disable zones, one at a time.  A flashing cursor appears next 
to the Z, prompting the programmer to enter a two digit zone number (01 - 99).  When the second 
digit is entered, the zone will be disabled and the cursor will return to the original position next to 
the Z.  Another zone can then be disabled.
Zone 97, 98 and 99
Pressing 3 for Zone 97, 98 and 99, while viewing Zone Setup Screen #1, will display the following 
screen: 
Zones 97, 98 and 99 can be programmed for normal zone operation or for special purpose applica-
tions.  In the above illustration, the three zones are shown Off, which means they can be pro-
grammed to function in the same manner as all other zones, by assigning them to input and output 
devices in the Programming Zone Assignment Screen.
Pressing 1 will cause the display to change to PAS 97 On.  Each press of the 1 key will cause the 
display to toggle between PAS 97 On and PAS 97 Off.  When Zone 97 is programmed On, a PAS 
(Positive Alarm Sequence) activation of any detector will cause Zone 97 to activate.  By assigning 
Zone 97 to a control module in the Programming Zone Assignment Screen, an output device con-
nected to the control module can be used to indicate a PAS condition in the control panel.  Do not 
assign Zone 97 to a Notification Appliance Circuit when using this zone to indicate a PAS condi-
tion. 
Pressing 2 will cause the display to change to Pre-signal 98 On.  Each press of the 2 key will cause 
the display to toggle between Pre-signal 98 On and Pre-signal 98 Off.  When Zone 98 is pro-
grammed On, a Pre-signal activation of any device will cause Zone 98 to activate.  By assigning 
Zone 98 to a control module in the Programming Zone Assignment Screen, an output device con-
nected to the control module can be used to indicate a Pre-signal condition in the control panel.  Do 
not assign Zone 98 to a Notification Appliance Circuit when using this zone to indicate a Pre-signal 
condition.
Pressing 3 will cause the display to change to Two Stage 99 On.  Each press of the 3 key will cause 
the display to toggle between Two Stage 99 On and Two Stage 99 Off.  Refer to “Two Stage Opera-
tion” on page 111
 for a description of this feature.
    ZONE SETUP
1=ENABLE
2=DISABLE
3=ZONE 97 98 99
Zone Setup Screen #1
  ZONE TO DISABLE
Z
Disable Screen
 SPEC PURPOSE ZONE
1=PAS 97        OFF
2=PRESIGNAL 98  OFF
3=TWO STAGE 99  OFF
Zone 97, 98 and 99 Screen