Installation
Hearthpad
Floor
Pedestal
Woodstove
Optional
fan
Outside air connection
through wall or floor
Chimney
connector
Ceiling
Insulated chimney
Roof flashing
Roof
Roof radiation
shield (if required)
Minimum air space
in accordance with
chimney manufacturer.
Wall support
Chase
(optional)
Insulated corner
Minimum
18" (475 mm)
Rain cap/
Spark arrestor cap
Storm Collar
and in any area within 10 feet 
(304.8  cm)  of  the  roof  ridge, 
the  chimney  must  be  2  feet 
(60.9  cm)  above  the  ridge. 
Refer to Figure 24.
Note:  Increasing  the  chimney 
height  above  the  roof  may 
help  your  unit  to  draft  better. 
This greater draft can decrease 
problems  such  as  difficult 
start-ups,  smoke  coming  out 
when  door  is  open,  and  dirty 
glass.  You  may  initially  try 
the  minimum  required  height 
and if problems do arise, add 
additional height later.
10. Slide  the  roof  flashing  over 
your  chimney  and  seal  the 
flashing  to  the  roof  with  a 
roofing compound. Secure the 
roof flashing to your roof with 
nails or screws.
11. Place the storm collar over the 
flashing and seal the joints 
with silicone caulking.
12. Fasten  the  rain  cap  /  spark 
arrestor cap to the top of your 
chimney.
13. Place  the  stove  back  into 
Figure 26: Standard Horizontal Installation.
position.
14. Install the chimney connector pipe with the lower (crimped) edge of the pipe inside the flue collar. 
Any  creosote  formed  will  then  run  back  down  into  the  stove.  All  connections  must  be  tight  and 
secured with three sheet metal screws equally spaced. Double wall pipe is recommended over single 
wall.
15. Also install an outside air flex pipe to the stove.
IMPORTANT: When a metal prefabricated chimney is used, the manufacturer’s installation instructions 
must be followed. You must also purchase and install the ceiling support package or wall pass-through 
and “T” section package, firestops (where needed), insulation shield, roof flashing, chimney cap, etc. 
Maintain proper clearance to the structure as recommended by the manufacturer. The chimney must be 
the required height above the roof or other obstructions for safety and proper draft operation.
Note: If you are using a horizontal connector (refer to Figure 26), the chimney connector 
should  be  as  high  as  possible  while  still  maintaining  the  18”  (475  mm)  minimum 
distance from the horizontal connector to the ceiling.
26