VR8104, VR8204 AND VR8304 INTERMITTENT PILOT COMBINATION GAS CONTROLS
3
69-1225—4
SPECIFICATIONS
Body Pattern: Straight through; see Table 1 for inlet and 
outlet size.
Electrical Ratings:
Voltage and Frequency: 24 Vac, 60 Hz.
Current Draw: 0.5A with both operators energized.
Capacity: See Table 1.
Conversion: Use conversion factors in Table 2 to con-
vert capacities for other gases.
Regulation Range: See Table 1.
Natural-LP Gas Conversion Kits: See Table 5.
Table 5.  Natural-LP Gas Conversion Kits.
Pipe Adapters:
Angle and straight adapters available for 3/8-, 1/2- and 
3/4-in. pipe. See Table 6. Flange kits include one 
flange with attached O-ring, four mounting screws, a 
9/64 in. hex wrench and instructions.
Approvals:
American Gas Association Design Certificate: L2025006.
Canadian Gas Association Design Certificate: L2025006.
Australian Gas Association Design Certificate: 4214.
Approved for Delta C applications.
European Community (CE) Certificate: Pending.
PLANNING THE INSTALLATION
WARNING
Fire or Explosion Hazard.
Can cause property damage, severe injury, 
or death.
Follow these warnings exactly:
1. Plan the installation as outlined below.
2. Plan for frequent maintenance as described in 
the Maintenance section.
Table 6. Flange Adapter Part Numbers.
a
Flange kits include one flange, one O-ring and four 
mounting screws.
b
Do not use flanges on control models with 3/4 in. inlet 
and 3/4 in. outlet. On models with 1/2 in. inlet and 
3/4 in. outlet, use flanges only on the 1/2 in. inlet side.
Heavy demands are made on the controls when 
intermittent pilot systems are used on central heating 
equipment in barns, greenhouses, and commercial 
properties and on heating appliances such as 
commercial cookers, agricultural equipment, industrial 
heating equipment and pool heaters. 
Special steps may be required to prevent nuisance 
shutdowns and control failure due to frequent cycling, 
severe environmental conditions related to moisture, 
corrosive chemicals, dust or excessive heat. These 
applications require Honeywell Home and Building 
Control Engineering review; contact your Honeywell 
Sales Representative for assistance.
Review the following conditions that can apply to your 
specific installation and follow the precautions 
suggested.
Frequent Cycling
This control is designed for use on appliances that 
typically cycle three to four times an hour only during the 
heating season. In year-around applications with greater 
cycling rates, the control can wear out more quickly. 
Perform a monthly checkout.
Water or Steam Cleaning
If a control gets wet, replace it. If the appliance is likely to 
be cleaned with water or steam, protect (cover) the 
control and wiring from water or steam flow. Mount the 
control high enough above the bottom of the cabinet so it 
does not get wet during normal cleaning procedures.
High Humidity or Dripping Water
Dripping water can cause the control to fail. Never install 
an appliance where water can drip on the control. In 
addition, high ambient humidity can cause the control to 
corrode and fail. If the appliance is in a humid 
atmosphere, make sure air circulation around the control 
is adequate to prevent condensation. Also, regularly 
check out the system.
Model No. 
Suffix Letter
Kit to Convert 
Natural Gas to LP
Kit to Convert LP 
to Natural Gas
H, K, M
393691
394588
P
Not field 
convertible.
Not field 
convertible.
Q
396021
396025
R
Not required, 
convertible valve.
Not required, 
convertible valve.
Inlet/Outlet 
Pipe Size 
(in. NPT)
Flange 
Type
Part Number
a,b
Without Hex 
Wrench
With Hex 
Wrench
3/8
Straight
393690-1
393690-11
3/8
Elbow
393690-2
393690-12
1/2
Straight
393690-6
393690-16
1/2
Elbow
393690-3
393690-13
3/4
Straight
393690-4
393690-14
3/4
Elbow
393690-5
393690-15