Sanyo CG1411 Manual Do Utilizador

Página de 100
61
Normal
ORG – ORG  DC 90 – 120 V
Normal
WHT – WHT  1 – 2.5 k
Ω
Normal
ORG – ORG  1 – 2.5 k
Ω
In case of abnormality 
Replace heating electromagnetic valve.
Disconnect heating gas valve (GV1, CN08) connector, and measure resistance at connector.
In case of abnormality 
Replace outdoor unit PCB.
3) Check electromagnetic valve (GV2) of the combination gas valve.
Measure DC voltage at electromagnetic valve connector (CN08) (under heating operation, during combustion).
In case of abnormality 
Replace heating electromagnetic valve.
Disconnect heating electromagnetic valve connector (CN08), and measure resistance at connector.
Normal
AC 104 – 126 V
In case of abnormality 
Replace outdoor unit PCB.
4) Check proportional control valve (PV).
Measure DC voltage at proportional valve connector (CN11) (under heating operation, during combustion).
In case of abnormality 
Replace flame rod.
5) Check flame rod.
Check if flame rod connector (CN17, 1P) is connected properly.
Measure AC voltage between flame rod connector and ground.
*
Use a circuit tester (set to 
Ω
range).
*
Use a circuit tester (set to 
Ω
range).
Normal
BLU – BLU  DC 5 – 30 V
*
Use a circuit tester (set to DC range).
*
Use a circuit tester (set to AC range).
*
Use a circuit tester (set to DC range).
In case of abnormality 
Replace flame rod.
Disconnect flame rod connector (CN17) and measure direct current at connector.
Normal
DC 2µA or more
*
Use a circuit tester (set to DC range).
12-6-6.  Erroneous Flame-Out Condition
Failure Display on Outdoor Unit PCB: 
● 
● ●
●  ●
Check in same manner as “Failure Display 
● ● ●
.”