SERIES 2000 ELECTRONIC TEMPERATURE SENSORS
9
63-2590—05
C7021J, C7023J, C7031J, C7041J MOUNTING
Fig. 11. Duct cross section showing method of installing 
C7021J, C7023J, C7031J, C7041J Averaging Electronic 
Sensor.
1. Install two supports inside the duct to hold the averaging 
element.
2. Cut a 7/8 in. (22 mm) hole in the side of the duct to insert 
the averaging element.
3. Fasten the terminal box to the outside of the duct and 
thread the element through the hole and into the duct.
4. Use plastic wire ties to fasten the element to supports. 
Seal the hole around the element with a rubber 
grommet.
5. Secure the end of the element to the duct on the 
support to prevent continuous flexing or abrasion.
IMPORTANT
To assure that the C7021J, C7023J, C7031J, C7041J 
senses average duct temperature, position the 
temperature elements approximately as shown in Fig. 
11. Do not allow the elements to touch or be close to 
the duct sides.
NOTE: When the sensor is used as a deck sensor in a 
multizone system, be sure to space the elements 
equally in the duct midstream as shown in Fig. 12.
Install one C7021J, C7023J, C7031J, C7041J just upstream 
from the cold deck zone dampers and the other C7021J, 
C7023J, C7031J, C7041J upstream from the hot deck zone 
dampers. Position the thermistors to sense the average deck 
temperature.
Fig. 12. Duct cross section showing method of installing 
C7021J, C7023J, C7031J, C7041J in a multizone system.
C7021R, C7023R, C7041R MOUNTING
1. Install two supports inside the duct to hold the 
averaging element.
2. Cut a 7/8 in. (22 mm) hole in the side of the duct.
3. Insert the averaging element into the duct through the 
hole.
4. Fasten the terminal box to the outside of the duct and 
thread the element through the hole and into the duct.
5. Use plastic wire ties to fasten the element to the 
supports. Seal the hole around the element with a rubber 
grommet.
6. Secure the end of the element to the duct on the 
support to prevent continuous flexing or abrasion.
Fig. 13. Duct cross section showing method of installing 
C7021R, C7023R, C7041R Averaging Electronic Sensor.
IMPORTANT
To ensure that the C7021R, C7023R, C7041R senses 
average duct temperature, position the temperature 
elements approximately as shown in Fig. 13. Do not 
allow the elements to touch or be close to the duct 
sides.
NOTE: When the sensor is used as a deck sensor in a 
multizone system, be sure to space the elements 
equally in the duct midstream as shown in Fig. 14.
Install one C7021R, C7023R, C7041R just upstream from the 
cold deck zone dampers and the other C7021R, C7023R, 
C7041R upstream from the hot deck zone dampers. Position 
the thermistors to sense the average deck temperature.
Fig. 14. Duct cross section showing method of installing 
C7021R, C7023R, C7041R in a multizone system.
M8929A
SENSING ELEMENTS (4)
DUCT
GROMMET
(NOT
INCLUDE)
SENSOR
SUPPORTS (2)
PLASTIC 
TIES (5)
M8928A
SENSING ELEMENTS (4)
DUCT
GROMMET
(NOT FURNISHED)
SENSOR
M22820
COPPER TUBING 
WITH SENSING 
ELEMENTS (4 OR 9)
DUCT
SENSOR
SUPPORTS (2)
PLASTIC 
TIES (5)
NUMBER OF ELEMENTS DEPENDS 
ON LENGTH OF COPPER TUBING.
1
1
M22819
DUCT
SENSOR
COPPER TUBING WITH 
SENSING ELEMENTS (4 OR 9)
NUMBER OF ELEMENTS DEPENDS 
ON LENGTH OF COPPER TUBING.
1
1