A
Building Safety. Building Security.
•   ADM loop technology with 
System Sensor/200 protocol
•   Transmitter and receiver unit 
integrated into one housing
•   Detection of clear and dark smoke
•  6 sensitivity levels selectable
•  Test fi lter for optimum commissioning
•   Automatic drift compensation
Description
With a range of 5m to 70m the Beam Smoke Detector 
6500 serves for the monitoring of open spaces. The 
transmitter/receiver unit projects a pulsed infrared light 
beam through the area to be protected towards a refl ec-
tor, which returns the light beam. The smoke detection 
is based on the attenuation of the light beam by means 
of smoke.
The  detector  uses  intelligent  evaluation  algorithms  to 
compensate for the infl uence of contamination of the 
optical measurement system. With that, the response 
sensitivity of the detector is kept constant for a long 
time – an effective step to avoid false alarms.
The  Beam  Smoke  Detector  6500  does  not  need  an 
external power supply and can be connected directly 
to the ADM loop with System Sensor/200 protocol. An 
integrated dual-isolator can be activated by removing 
two jumpers.
The  response  sensitivity  of  the  detector  can  be  set 
to one of six levels. Four levels have a fi xed response 
threshold, whereas two further levels with variable re-
sponse sensitivity allow to adjust the detector to chan-
ging environmental conditions.
The detector is delivered with a refl ector, which can be 
used for ranges from 5m to 70m. A three-part refl ector 
set, which extends the range of the detector to 100m, 
is available as accessory.
The Beam Smoke Detector 6500S corresponds to the 
Beam Smoke Detector 6500 in design and function. In 
addition,  the  6500S  can  be  remotely  activated  from 
the fi re detection control panel, allowing easy function 
testing  during  maintenance.  This  test  simulates  light 
obscuration by means of a motor-driven test fi lter. An 
external power supply is needed for the test unit, which 
can not be powered by the loop.