LST FWI016-1 Folheto

Página de 1
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
FWI016-1_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
Description
The Fire Brigade Interface FWI016 allows for the con-
nection of two independent transmitting devices for di-
rect interconnection to a designated alarm respondent 
(e.g., the fi re brigade) as well as the connection of a 
country specifi c fi re brigade control unit to Fire Detec-
tion Control Panels Series BC016.
A dry contact and a line-monitored output are available 
for the connection of the transmitting devices.
The parameters of the eight inputs and seven outputs 
can also be freely set and thus are available for general 
control tasks.
•   Relay output with dry changeover 
contact
•   Line-monitored output with selectable 
surveillance current
•   8 inputs and 7 outputs for control 
tasks
•   Connection of country-specifi c fi re 
brigade control units
Specifi cations
Current consumption at 24V 
typ. 4mA
Contact rating of relay contact 
60V/1A/30W
Contact life 
approx. 300,000 switching cycles (at 24VDC/1A)
Ambient temperature 
-5°C to +50°C
Dimensions L × W × H 
130 × 65 × 15 (mm)
Weight 
70g
Part No. 
210111
Order name 
Fire Brigade Interface FWI016-1