Building Safety. Building Security.
Description
The Thermal ROR Detector ECO1005 reacts to tem-
perature  changes  within  defi ned  periods  of  time,  up 
to  a  maximum  temperature  of  58°C.  The  intelligent 
evaluation of these data allows the early detection of 
spreading fi res.
Addressable conventional technology is used for alarm 
transmission  to  the  fi re  detection  control  panel.  By 
means of the Address Module NG58-1, each detector 
can be addressed individually.
A  test  activation  of  the  detector  can  be  carried  out 
using the Remote Test Unit ECO1000RTU. The detec-
tor can be attached to various detector bases and it 
can be protected against theft.
•  Addressable conventional technology
•   Maximum temperature 58°C
•   Individual detector addressing by 
means of optional address module
•   Optional connection of remote 
indicator
•   Function testable with Remote Test 
Unit ECO1000RTU
Specifi cations
Operating voltage 
Supply through the detector line voltage
Current consumption 
typ. 75µA (quiescent)
Alarm temperature 
58°C (maximum-heat component)
Operating temperature 
max. +45°C
Ambient temperature 
-30°C to +70°C
Relative humidity 
5 – 95% (no condensation)
Dimensions ø × H 
102 × 40.5 (mm)
Colour 
white
Weight 
70g
Approval 
VdS G201016
Order number 
242045
Order name 
Thermal ROR Detector/Conv./1000/SS ECO1005