LST ECO1004T Folheto

Página de 1
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED
ECO1004T_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
•  Addressable conventional technology
•   Alarm temperature 78°C
•   Individual detector addressing by 
means of optional address module
•   Optional connection of remote 
indicator
•   Function testable with Remote Test 
Unit ECO1000RTU
Description
The  Thermal  Max  Detector  ECO1004T  recognises  a 
maximum temperature of 78°C as sign of fi re. It com-
plies  with  Class  BS  and  can  be  used  up  to  a  room 
height of 6m.
Addressable conventional technology is used for alarm 
transmission  to  the  fi re  detection  control  panel.  By 
means of the Address Module NG58-1, each detector 
can be addressed individually.
A  test  activation  of  the  detector  can  be  carried  out 
using the Remote Test Unit ECO1000RTU. The detec-
tor can be attached to various detector bases and it 
can be protected against theft.
Specifi cations
Operating voltage 
Supply through the detector line voltage
Current consumption 
typ. 75µA (quiescent)
Alarm temperature 
typ. 78°C
Operating temperature 
max. +60°C
Ambient temperature 
-30°C to +70°C (continuous operation)
Relative humidity 
5 – 95% (no condensation)
Dimensions ø × H 
102 × 40.5 (mm)
Colour 
white
Weight 
70g
Approval 
VdS G202042
Order number 
242047
Order name 
Thermal Max Detector/Conv./1000/SS ECO1004T