Enviro C-10078 Manual Do Utilizador

Página de 42
17
3½" (89mm)
8" (203mm) mantel
Combustibles
Cement Board
DV42DX
10"
(254mm)
12"
(305mm)
17"
(432mm)
20"
(508mm)
8" (203mm) mantel
Combustibles
Cement Board
DV42DX
with Manor
10"
(254mm)
12"
(305mm)
17"
(432mm)
Figure 23.  Combustible Mantel Clearances for The 
Manor 
Figure 22.  Combustible Mantel Clearances.
Initial Installation
QUALIFIED INSTALLERS ONLY
m
anteL
 c
LeaRances
:
It is not necessary to install a mantel, but if one is desired it is important to follow the guidelines shown 
in Figure 22. The Manor face has a different set of mantel clearances than the other faces, see 
Figure 23. 
Figure 24.  Vent Termination Restrictions, refer to Table 2.
v
ent
 t
eRmination
 R
estRictions
:
A
A
D E
L
B
C
F
B
B
B
J
M
K
G
H
I
Openable
Fixed
Closed
Openable
Fixed
Closed
Termination Cap
Air Supply Inlet
Gas Meter
G
G
Restriction Zone
(Termination not allowed)
N
O