For  the  first  24  inches  (610  mm)  of 
ducting, ½ inch (13 mm) of clearance 
is  required.  After  24  inches  (610  mm), 
the  duct  can  be  run  with  0  inch  (0  mm) 
clearance,  though  ½  inch  (13  mm)  is 
preferred.  To  avoid  heat  loss,  insulate 
the  duct  whenever  it  passes  through  an 
unheated area (i.e. crawl space). Insulating 
the ducts elsewhere helps the efficiency of 
the ducting system.
Standard  galvanized  ducting  and  heat 
registers  are  to  be  used.    Simply  remove 
the desired cover plate from the outside of 
the firebox and attach a 6 inches (152 mm) 
starter ring. Make sure to foil-tape all seams 
to prevent leaking. Ensure all ducting meets 
local building codes.
Figure 38. Ducting Options; ducted from 
upper floor to lower floor & from lower floor 
to upper floor.
Figure 39. More Ducting Options; ducted to outside & to 
another room on an interior wall.
Initial Installation
QUALIFIED INSTALLERS ONLY
D
ucting
:
The option of ducting allows heat from the fireplace to be transferred to a different area. The maximum 
total length for the ducting is 20 feet (6.1 m). There are four (4) duct outlets that can be used (see Figure 
37), however, the blower puts out 200 cfm no matter how many ducts are used. Therefore, the more 
ducts there are, the less air goes through each one. A short, straight duct maximizes its heating ability 
as air in the ducts is restricted by the length and number of bends in the pipe. 
Figure 37. Heat Dumping Options.