Condenser Return Line 
Shut-Off Valve
Condenser Return Line 
Drain Valve
Icemaker
Drain Outlet 
3/4" FPT
Icemaker 
Water Supply 
Inlet
1/" FPT
Condenser 
Water Supply 
Inlet
1/" FPT
Condenser 
Return Outlet 
1/" FPT
Separate piping to approved drain. 
Leave a two-inch (5 cm) vertical air 
gap between the end of each pipe 
and the drain.
Icemaker
Bin Drain Outlet 
3/4" FPT
Two-inch 
(5 cm) air 
gap
Floor Drain
Bin
Icemaker Water Supply 
Line Shut-Off Valve
Icemaker Water Supply Line 
Drain Valve
Condenser Water Supply Line 
Shut-Off Valve
Condenser Water Supply Line 
Drain Valve
b) Connection to a Closed Loop System 
• Condenser water supply inlet is 1/" female pipe thread (FPT). A minimum of 3/8" OD 
copper tubing is recommended for the condenser water supply line.
• Condenser return outlet is 1/" FPT. A minimum of 3/8" OD hard pipe is recommended for 
the condenser return line.
• Shut-off valves and drain valves should be installed at both the condenser water supply 
inlet and condenser return outlet.
• The water supply to the condenser should not drop below 4 GPM. 
• The pressure differential between the condenser water supply inlet and condenser return 
outlet must be no less than 10 PSIG.
• When using a glycol blend, the solution mixture should be less than 30% glycol.
• In order to maintain the proper high side pressure, the condenser water supply inlet 
temperature should not drop below 45°F (7°C) and the condenser return outlet 
temperature must be in the 104°F to 115°F (40°C to 46°C) range. Once the icemaker 
installation is complete, confirm the condenser return outlet temperature 5 minutes 
after a freeze cycle starts. If the outlet temperature is not in the proper range, adjust the 
water-regulating valve to bring it into range.
Fig. 9
KMD-450MWH 
Connection to a Closed Loop System