Cisco Nexus 7000 6.0kW AC Power Supply Module N7K-AC-6.0KW Ficha De Dados
Códigos do produto
N7K-AC-6.0KW
Data Sheet
© 2008-2009 Cisco Systems, Inc. All rights reserved. This document is Cisco Public Information.
Page 5 of 8
Internal fault monitoring
Detects short circuits and component failures within the power supply unit; if a failure is
found, the unit is shut down
found, the unit is shut down
Intelligent remote
management
management
Users can remotely power cycle one or all power supplies using the supervisor command-
line interface (CLI), enabling remote management and improving operational efficiency (not
available at initial software release)
line interface (CLI), enabling remote management and improving operational efficiency (not
available at initial software release)
Real-time power draw
Shows real-time actual power consumption (not available at initial software release)
Variable fan speed
Allows reduction in fan speed for lower power use in well-controlled environments while
helping ensure sufficient system cooling capacity
helping ensure sufficient system cooling capacity
Product Specifications
Table 8 lists production specifications for the Cisco Nexus 7000 Series AC Power Supply Modules,
and Tables 9 and 10 lists the cable specifications.
Table 8.
Product Specifications
Specification
Power Supply
6.0kW AC Power Supply
7.5kW AC Power Supply
Chassis compatibility
●
Cisco Nexus 7010 (up to 3)
●
Cisco Nexus 7018 (up to 4)
Software compatibility
Cisco
®
NX-OS Software Release 4.0 and
later
Cisco NX-OS Software Release 4.1(2) and
later
later
Physical specifications
●
(H x W x D): 8.51* x 4 x 17.5 in. (21.6 x
10.1 x 44.5 cm)
●
Weight: 18 lb (8.2 kg)
●
* The height of the power supply unit is
not uniform along the entire depth. The
height at the front and rear are 8.51 and
4.2 in. (21.6 and 10.7 cm) respectively.
height at the front and rear are 8.51 and
4.2 in. (21.6 and 10.7 cm) respectively.
●
(H x W x D): 8.51* x 4 x 17.5 in. (21.6 x
10.1 x 44.5 cm)
●
Weight: 23 lb (10.5 kg)
●
* The height of the power supply unit is
not uniform along the entire depth. The
height at the front and rear are 8.51 and
4.2 in. (21.6 and 10.7 cm) respectively.
height at the front and rear are 8.51 and
4.2 in. (21.6 and 10.7 cm) respectively.
Input voltage range
90 to 264 VAC
170 to 264V AC
Input frequency range
47 to 63 Hz
47 to 63 Hz
Input current (each input)
16A maximum at nominal line voltage (110
or 220 VAC)
or 220 VAC)
24A maximum at nominal line voltage (220
VAC)
VAC)
Power supply input
receptacles
receptacles
International Electrotechnical Commission
(IEC) 320-C19
(IEC) 320-C19
IEC 60309 for INT
NEMA L6-30 for US
Power cord rating
16A
24A
British thermal units (BTUs)
●
23,000 BTUs per hour at 6000W
●
16,500 BTUs per hour at 4200W
●
11,500 BTUs per hour at 3000W
●
9900 BTUs per hour at 2400W
●
4950 BTUs per hour at 1200W
●
28500 BTUs per hour at 7500W
●
14200 BTUs per hour at 3750W
Mean time between failure
(MTBF)
(MTBF)
341,356 hours
204,053 hours
Output holdup time
20 milliseconds (ms) minimum
Cooling fan
Integrated
Environmental conditions
●
Operating temperature: 32 to 104°F (0 to 40°C)
●
Storage temperature: –40 to 185°F (–40C to 85°C)
●
Relative humidity operating, noncondensing: 10 to 90%
●
Relative humidity nonoperating, noncondensing: 10 to 95%
Regulatory compliance
●
EMC compliance
●
FCC Part 15 (CFR 47) (USA) Class A
●
ICES-003 (Canada) Class A
●
EN55022 (Europe) Class A
●
CISPR22 (International) Class A
●
AS/NZS CISPR22 (Australia and New
Zealand) Class A
●
VCCI (Japan) Class A
●
KN22 (Korea) Class A