Empire Comfort Systems VFD26F3-1 Manual Do Utilizador

Página de 32
Page 11
23466-0-0407
Check all local codes for requirements, especially for the size and 
type of gas supply line required.
Recommended Gas Pipe Diameter
Pipe Length
Schedule 40 Pipe
Inside Diameter
Tubing, Type L 
Outside Diameter
Nat.
L.P.
Nat.
L.P.
0-10 feet
0-3 meters
1/2”
12.7mm
3/8”
9.5mm
1/2”
12.7mm
3/8”
9.5mm
10-40 feet
4-12 meters
1/2”
12.7mm
1/2”
12.7mm
5/8”
15.9mm
1/2”
12.7mm
40-100 feet
13-30 meters
1/2”
12.7mm
1/2”
12.7mm
3/4”
19mm
1/2”
12.7mm
100-150 feet
31-46 meters
3/4”
19mm
1/2”
12.7mm
7/8”
22.2mm
3/4”
19mm
Note: Never use plastic pipe. Check to confirm whether your local 
codes allow copper tubing or galvanized.
Note: Since some municipalities have additional local codes, it is 
always best to consult your local authority and installation code.
Installing a New Main Gas Cock 
Each appliance should have its own manual gas cock.
A  manual  main  gas  cock  should  be  located  in  the  vicinity  of 
the unit. Where none exists, or where its size or location is not 
adequate, contact your local authorized installer for installation 
or relocation.
Compounds used on threaded joints of gas piping shall be resistant 
to the action of liquefied petroleum gases. The gas lines must be 
checked for leaks by the installer. This should be done with a soap 
solution watching for bubbles on all exposed connections, and if 
unexposed, a pressure test should be made. 
Never use an exposed flame to check for leaks. Appliance must 
be disconnected from piping at inlet of control valve and pipe 
capped or plugged for pressure test. Never pressure test with 
appliance connected; control valve will sustain damage!
A gas valve and ground joint union should be installed in the gas 
line upstream of the gas control to aid in servicing. It is required 
by the National Fuel Gas Code that a drip line be installed near 
the gas inlet. This should consist of a vertical length of pipe tee 
connected into the gas line that is capped on the bottom in which 
condensation and foreign particles may collect.
The use of the following gas connectors is recommended:
—  ANS Z21.24 Appliance Connectors of Corrugated Metal Tub-
ing and Fittings
—  ANS  Z21.45 Assembled  Flexible Appliance  Connectors  of 
Other Than All-Metal Construction
The above connectors may be used if acceptable by the authority 
having jurisdiction. The state of Massachusetts requires that a flex-
ible appliance connector cannot exceed three feet in length.
Pressure Testing of the Gas Supply System
1.   To check the inlet pressure to the gas valve, a 1/8" (3mm) N.P.T. 
plugged tapping, accessible for test gauge connection, must 
be placed immediately upstream of the gas supply connection 
to the appliance.
2.  The  appliance  and  its  individual  shutoff  valve  must  be 
disconnected from the gas supply piping system during any 
pressure testing of that system at test pressures in excess of 
1/2 psig (3.5 kPa).
3.   The appliance must be isolated from the gas supply piping 
system by closing its individual manual shutoff valve during 
any pressure testing of the gas supply piping system at test 
pressures equal to or less than 1/2 psig (3.5 kPa).
Figure 7
Attention! If one of the above procedures results in pressures in 
excess of 1/2 psig (14" w.c.) (3.5 kPa) on the appliance gas valve, 
it will result in a hazardous condition.
Checking Manifold Pressure
(A)VFD26F(M,P)3 Natural gas will have a manifold pressure of 
approximately 3.5" w.c. (.871kPa) for maximum input or 1.7" w.c. 
(.423kPa) for minimum input at the pressure regulator outlet with 
the inlet pressure to the pressure regulator from a minimum of 5.0" 
w.c. (1.120kPa) for the purpose of input adjustment to a maximum 
of 10.5" w.c. (2.614kPa). 
(A)VFD26F(M,P)2 Natural gas will have a manifold pressure of 
approximately 6.0" w.c. (1.49kPa) at the pressure regulator outlet 
with the inlet pressure to the pressure regulator from a minimum 
of 7.0" w.c. (1.74kPa) for the purpose of input adjustment to a 
maximum of 10.5" w.c. (2.615kPa). 
(A)VFD26F(M,P)3  Propane  gas  will  have  a  manifold  pressure 
approximately  10.0"w.c.  (2.49kPa)  for  maximum  input 
or  6.3"w.c.  (1.568kPa)  for  minimum  input  at  the  pressure 
regulator outlet with the inlet pressure to the pressure regulator 
from  a  minimum  of  11.0"w.c.  (2.739kPa)  for  the  purpose 
of  input  adjustment  to  a  maximum  of  13.0"w.c.  (3.237kPa).  
(A)VFD26F(M,P)2  Propane  gas  will  have  a  manifold  pressure 
approximately 10.0"w.c. (2.49kPa) at the pressure regulator outlet 
with the inlet pressure to the pressure regulator from a minimum 
of 11.0"w.c. (2.739kPa) for the purpose of input adjustment to a 
maximum of 13.0"w.c. (3.237kPa). 
GAS SUPPLY