15
b) For Freezers
This unit is preset at the factory to defrost 6 times per day for general conditions. Note 
that the defrost is a heated defrost, and therefore will have a tendency to raise the 
cabinet temperature. Cabinet temperature is not displayed during defrost; "dEF" is 
displayed in its place. When a sensor in the evaporator coil reaches the termination 
setpoint, the unit ends defrost. After defrost, there is a 5 minute delay before the 
compressor will start.
Before changing the defrost frequency setting, contact the Hoshizaki Technical Support 
Department at 1-800-33-1940 for recommendations. If necessary, adjust the defrost 
frequency as follows:
1) Press and hold the up/down arrows simultaneously for 3 seconds. Press "ENTER" until 
the dF frequency is displayed.
) To change the time-initiated defrost frequency, press the up/down arrows until the 
desired value is displayed. The defrost frequency is adjustable between 1 and 8 
defrosts per 4 hours. The factory default is 6.
3) To save the value, press "ENTER" repeatedly until you have cycled through the menu 
and the unit returns to the normal display mode. If you do not cycle through the menu 
and no button is pressed in 15 seconds, the display will return to normal and the 
defrost frequency will remain unchanged.
Note: The change in the defrost setting will take effect after the next defrost based 
on the previous setting. To make this change in interval timing take effect 
immediately, turn the unit off and back on. The next defrost will take effect "x" 
hours after power is resupplied. For example, if set df 6, x=4, the next defrost will 
take place 4 hours from the time that power is applied.
2. SafeTemp Models
a) For Refrigerators
This unit uses an off-cycle defrost. A sensor in the evaporator coil determines the need 
for a defrost. When the sensor reaches the initiation setpoint, the unit enters defrost. 
When the unit reaches the termination setpoint, the unit ends defrost. After defrost, there 
is a 5 minute delay before the compressor will start. The off-cycle defrost requires no 
programming; it automatically initiates and terminates.
b) For Freezers
This unit is preset at the factory to defrost 6 times per day for general conditions. Note 
that the defrost is a heated defrost, and therefore will have a tendency to raise the 
cabinet temperature. Cabinet temperature is not displayed during defrost; "dEF" is 
displayed in its place. When a sensor in the evaporator coil reaches the termination 
setpoint, the unit ends defrost. After defrost, there is a 5 minute delay before the 
compressor will start. When the compressor starts, the display changes to "rEC". Once 
the cabinet thermistor drops to 15°F above the setpoint, the display reverts back to 
cabinet temperature.